Sizing 2-3 seconds of backup power for a controlled servo stop

Control power: 24 V DC, UPS and transformers Published 8 min read By Current Intel engineering team

Short answer

At the estimated 5 kW held for 3 s the load-side need is 15 kJ, so specify a source that delivers the stop power with 20 kJ usable after losses and reserve. The choice between a three-phase on-line UPS and a 24 V control-power buffer alone comes from one fact: an axis set that regenerates during the stop needs no three-phase source at all.

On this page
  1. How much energy does a 2-3 second servo stop need?
  2. Do the axes draw power or generate it during the stop?
  3. Why can't the drive's own capacitors hold the stop?
  4. Which backup source fits: a three-phase UPS, DC-link storage or control power alone?
  5. How do I keep control power alive through the stop?
  6. When must the stop be triggered, and how fast should it decelerate?
  7. How do I measure the real stop power before buying?
  8. Questions asked

Size this by energy, not by the 480 V on the nameplate. At the estimated 5 kW held for the full 3 s, the load-side need is 15 kJ, and the source must deliver that while holding the stop power with no transfer gap. Whether you buy a three-phase on-line UPS, a DC-link storage module, or nothing bigger than a 24 V buffer depends on one quantity: the power flow during the stop. An axis set that regenerates as it decelerates stops itself through its brake choppers and needs only its control power held up; a friction-dominated stop needs the full source.

How much energy does a 2-3 second servo stop need? #

At the provisional load estimate held for the full 3 s, the load-side requirement is 15 kJ before losses and reserve, and the source must deliver that energy while holding the stop power at the same time. Energy and power are two separate constraints: a unit can store enough joules and still fail on its current limit, or deliver the current and run dry before the axes reach zero.

The arithmetic is E = P × t for a constant-power estimate: 5 kW × 3 s = 15 kJ at the long end of the window, 10 kJ at 2 s. Multiply by 1.25 for conversion losses and reserve and round up: 18.75 kJ, so specify 20 kJ usable, delivered at the load. For a three-phase input, voltage alone sets neither number — apparent power needs the line current, and real power needs the power factor on top of that.

Requirement Value to specify Basis
Delivered energy 20 kJ usable the load-side figure plus a quarter for losses and reserve
Delivered power the estimated stop power, held for the whole interval provisional machine estimate, replaced by the stop measurement
Transfer gap none; on-line conversion only the stop must begin at the outage instant
Deceleration time zero speed within 2 s leaves 1 s of the window in reserve
Reverse power sink it in a brake chopper or accept it decided by the stop measurement

Treat that table as the buy-to specification, then let the measured stop replace the estimate in it before the order goes out.

Do the axes draw power or generate it during the stop? #

A decelerating servo motor works as a generator, so the stop either returns kinetic energy to the DC link or draws energy when friction and process forces dominate, and which of the two your machine does decides the whole backup architecture. The stored mechanical energy is E = 0.5 × J × ω², with J the inertia referred to the motor shaft and ω the speed in radians per second. A descending vertical axis releases gravitational energy on top of that.

Worked through: an axis with J = 0.05 kg·m² at 3000 rpm has ω = 3000 × 2π/60 = 314 rad/s, so E = 0.5 × 0.05 × 314² ≈ 2.5 kJ. Four such axes hand back about 10 kJ during the ramp down — the same order as the energy the friction case draws from the source.

The fault record tells you which case you are in before you measure anything. A DC-link overvoltage during the stop means returned energy with nowhere to go; the chopper answers by switching its resistor in above a threshold bus voltage and burning the energy as heat. A supply undervoltage trip means the bus ran dry. On a PM servo axis the returned energy has to leave through that resistor, and why a motor-side braking resistor works on a PM servo explains the path and why the motor side is the place to watch.

The purchasing consequence: a conventional on-line UPS pushes power out and cannot accept reverse power, so on a net-generating machine its bus climbs and it trips. There the three-phase source is not just unnecessary — it is the wrong device.

Why can't the drive's own capacitors hold the stop? #

The drive's own DC-link capacitors hold only a small fraction of the stop energy inside their usable voltage window, so the bus collapses to the undervoltage trip long before the axes reach zero speed. Capacitor energy follows E = 0.5 × C × (V₁² − V₂²), and the window between V₁ and V₂ comes from the drive's manual for the exact model, not from you.

Example inputs: a 2000 µF bus allowed to fall from 650 V to 500 V stores E = 0.5 × 0.002 F × (650² − 500²) = 0.5 × 0.002 × 172,500 ≈ 172 J. Holding the whole stop in that same window would take C = 2 × 15,000 J / 172,500 V² ≈ 0.17 F — close to a hundred times the capacitance on the board. External storage that large is a real architecture, but only through an interface the drive's documentation supports, and it needs a precharge path into the bargain; sizing a precharge resistor for drive DC-link capacitance covers that calculation. Where the manual documents no external storage interface and no DC bus terminals, this route is closed.

Pick the on-line three-phase UPS for a stop that draws net energy, a manufacturer-supported DC-link storage module where the drive documents that interface, and a 24 V control-power buffer alone when the axes generate through the whole stop.

Option Fits when What it must deliver Reverse power Verify first
Three-phase on-line UPS at the drive input the stop draws net energy the stop power and usable energy specified above, no transfer gap not accepted; a conventional inverter trips on overvoltage output rating above the load's kVA at its power factor
Manufacturer-supported DC-link storage the manual documents an external storage interface energy sized by the bus-voltage window, plus precharge accepted inside the bus window the documented window, interface and precharge rules
Control-power buffer plus existing brake choppers the stop is net regenerative the control chain only sunk as heat in the chopper's resistor chopper pulse-energy and duty ratings
The drive's built-in ride-through function the exact model provides one nothing added handled by the drive the model's manual and its reaction settings

For the net-drawing machine the UPS energy is trivial: the specified 20 kJ is under 6 Wh, so any battery covers it — what you are buying is the double-conversion stage that keeps the output alive with no transfer gap. A line-interactive unit with a transfer time is the interruption you are paying to prevent. For the net-generating machine the UPS is the wrong purchase: the axes supply their own deceleration and the choppers dispose of it, so the money goes into the control chain instead.

How do I keep control power alive through the stop? #

Hold up every link in the control chain — the motion controller, the drive control electronics, the network and the holding brakes — because the bus energy is useless the moment the electronics that command the stop drop out. Say the chain measures 120 W at 24 V, controller, distributed I/O and drive control cards as example inputs. That is I = 120 W / 24 V = 5 A. Detection, the 2 s deceleration and final-state handling fit inside 4 s, so E = 120 W × 4 s = 480 J, and any capacitor-buffered module that holds 5 A for 4 s covers it. The brakes matter more than the average: the holding brake must still apply at zero speed, because reaching zero does not hold a suspended load.

One trap closes this route on some machines: drives whose control electronics feed from their own power input die with the supply, so a buffer on the controls does not save them — that machine is forced onto the UPS or the documented DC-link storage. Where the controls run from a control transformer off the main input, the chain design is its own job, and single phase control power for a three phase machine walks through that arrangement.

When must the stop be triggered, and how fast should it decelerate? #

Trigger the coordinated stop at the first sign of the interruption and program the deceleration to reach zero speed in 2 s, which keeps 1 s of the required interval in reserve for detection, command execution and final-state handling. Detection time is part of the budget: wire the backup source's relay contact, or the drives' own undervoltage signal, into the controller's stop input so the ramp begins at the outage instant rather than after a human notices.

The ramp itself lives in the drive's deceleration parameter group — set it to the table's figure, inside the travel the mechanics tolerate, and confirm the final state: brakes applied and axis enables dropped.

How do I measure the real stop power before buying? #

Record input power, DC-link voltage, axis speed and drive status through one controlled stop before you buy anything, because the sign of the net energy over that interval decides the architecture and the estimate alone cannot. Instrument the machine input with a power-quality recorder, read bus voltage and speed from the drives' diagnostics, and integrate power across the whole interval — detection, ramp and final state included. Net draw buys the UPS or the storage module; net return buys the control buffer and leaves the choppers their job. Where equipment keeps getting damaged across events, record the restoration waveform too: damage on re-energization is a transient problem, not an energy problem.

Fitting current probes or reaching DC bus terminals is de-energized work: lock out the feeder and test for absence of voltage before the cabinet opens, and run the stop test itself with the panels closed.

The decision for each case:

  • Stop draws net energy at the estimated load: three-phase on-line UPS at the drive input, rated above the load's kVA at its power factor, delivering the stop power and the 20 kJ specified above. A documented DC-link storage module is the equivalent alternative.
  • Stop returns net energy: no three-phase source. A control-power buffer sized on the measured chain, with the choppers checked against their pulse-energy and duty ratings for the stop.
  • Mixed axes on separate inputs: the UPS carries the drawing axes and the choppers carry the returning ones.
  • Mixed axes on a common DC bus: returning axes feed drawing axes across the bus, and dc bus sharing on servo drives gives the supply and filter rules that arrangement must follow.

Questions asked

How do I convert the 5 kW stop power into a UPS kVA rating?

Divide the stop power by the load's power factor: at 0.9, S = 5 kW / 0.9 = 5.6 kVA, and the line current at 480 V follows as I = 5600 VA / (1.732 × 480 V) ≈ 6.7 A per phase. Select the next standard rating above that apparent power and confirm the unit is true double conversion, because any transfer gap is itself the interruption the stop must survive.

Is a 24 V buffer module enough instead of a three-phase UPS?

Yes, whenever the stop is net regenerative. The axes feed their own deceleration and the brake choppers burn the returned energy, so only the control chain needs holding up. Size the buffer on the measured chain current plus the holding brakes' release current, which is often the largest single draw and arrives exactly when the stop begins.

Can I connect supercapacitors directly to the drive's DC bus terminals?

Only through an external storage interface the drive's own manual documents for that exact model; with no documented interface, do not connect anything to the bus terminals. Added capacitance also needs a precharge path sized for the new total, or the inrush at power-up trips the input protection or welds the contactor.

What if the supply returns while the axes are still stopping?

Latch the stop command in the controller so the sequence finishes before anything re-enables, and suppress automatic restart reactions for the duration. An uncontrolled re-enable mid-deceleration can command torque against an already-stopping axis and cause exactly the mechanical damage the backup was bought to prevent.

Keep reading

  • Explainer

    Why AC servo motors are three phase and where the brake goes

    A three-phase axis motor with a rear encoder is a closed-loop AC servo: its drive synthesizes the three phases, brakes the axis electrically on every stop, and handles the returned energy on its DC bus. A mechanical holding brake is not a stopping device — it only secures gravity-loaded axes such as a Z axis, is usually a factory-built motor option, and runs on a dedicated 24 V DC circuit.

    Variable frequency drives

  • Selection guide

    Frequency converter sizing when a single-phase load regenerates

    A standard diode-front-end frequency converter cannot pass reverse power to the supply, so a single-phase load regenerating into one line pair charges the DC bus until the overvoltage trip. Size on per-line current and reverse power, not net kilowatts, and select a four-quadrant active-front-end converter or a rotary set rated for continuous regeneration and the single-phase unbalance.

    Variable frequency drives

  • How-to

    Sizing a 480 to 120 V three-phase servo drive transformer

    Use a dry-type three-phase transformer with a 480 V primary and a 120 V secondary, sized kVA = 1.732 × 120 V × I_line / 1000 per amplifier and summed over the bank, then take the next standard size. Skip SCR-type regulators and energize with the amplifier disconnected, measuring all three secondary voltages first.

    Control power: 24 V DC, UPS and transformers