Current IntelPower LibraryShop main store

Selection guide

Sizing a soft starter for a 110 V single-phase freezer compressor

Motors and motor starters Published 8 min read

Short answer

Size the starter from the compressor's nameplate running current and starting duty, not the 45 A inrush; the 6 A from 660 W ÷ 110 V is only a unity-power-factor estimate. Reduced voltage cuts torque roughly with voltage squared, so pushing the start below the 30 A supply limit needs about 67% voltage and leaves roughly 44% torque, which makes the restart delay and pressure equalization decide success more than the starter's amp rating.

On this page
  1. The nameplate current, not the inrush, sets the size
  2. What each number can and cannot size
  3. Torque falls with voltage squared
  4. Verify the catalog model before the amps
  5. Restart delay lets the pressures equalize
  6. The decision, case by case
  7. Questions asked

Size the starter from the compressor's nameplate running current and the duty the start has to perform, not from the reported inrush. For this 660 W freezer on its single-phase 30 A supply, the right class is a single-phase soft starter rated at or just above the running current, and two checks decide whether it works at all: the catalog number must be a single-phase model, and the compressor must still make enough torque at reduced voltage to start against whatever refrigerant pressure difference exists at that moment. Where it cannot, a soft start turns a brief inrush into a longer heating event and the internal protector opens. The restart delay, which lets pressure equalize before each start, is part of the sizing decision.

The nameplate current, not the inrush, sets the size #

Read the compressor nameplate, not the appliance brochure. NFPA 70, the National Electrical Code, 2023 edition, covers hermetic refrigerant motor-compressors in Article 440, and its marking rule requires the nameplate to state the rated-load current and the locked-rotor current among other values; those two figures are your inputs. Confirm the requirement with the local authority having jurisdiction and the appliance documentation. The rated-load current is also the number you use when setting overload relays from motor nameplate full-load current, so one reading serves both decisions.

The running current is not simply wattage divided by voltage. At unity power factor, 660 W ÷ 110 V = 6 A. If the nameplate instead gives an input power factor of 0.85, the running current is 660 W ÷ (110 V × 0.85) ≈ 7.1 A, about 18% higher; if the watts are shaft output rather than electrical input, efficiency divides once more. Treat every such division as an estimate until the nameplate current replaces it.

The start itself is covered by the starter's documented starting duty, not by its nominal current. IEC 60947-4-1, the product standard for contactors and motor starters including semiconductor soft starters, defines that duty through utilization categories stating starts per hour, ramp time and the current multiple the unit is built for, which is why one amperage figure on a label cannot tell you whether it survives this compressor's start.

What each number can and cannot size #

Five numbers circulate on this job, and each answers a different question.

Quantity Value on this job What it sizes What it misses
Reported inrush 45 A Nothing on its own: an outcome, not a duty Ramp time, starts per hour, torque margin
Unity-power-factor estimate 6 A The starter's continuous-current class, first pass Power factor, input versus output watts
Supply rating 30 A (3.3 kVA) Whether a soft start is needed at all The protective device's time-current behavior
Proposed starter 25 A, catalog number ATS01N125FT Usable only if documented as a single-phase model Phase count, motor-type compatibility, start duty
Documented candidate ATS01N106FT, 110 to 480 V, 0.75 to 3 kW Matches the running-current class Compressor start duty, control wiring

One comparison settles whether the soft start is needed at all. The start demands 110 V × 45 A ÷ 1000 = 4.95 kVA against a 3.3 kVA supply, a momentary overrun of roughly 1.5 times the rating. A thermal-magnetic breaker typically rides through a fraction of a second at that level; a current-limited source, such as a small generator or an inverter, instead collapses its voltage. Which one you have is a measurement, not an opinion: record current and terminal voltage together during a direct-on-line start with a true-RMS clamp meter that captures inrush.

Torque falls with voltage squared #

A soft starter does one thing: it reduces voltage. For an induction machine near standstill, locked-rotor current falls roughly in proportion to voltage and locked-rotor torque roughly with its square. That trade has a hard floor on a compressor.

Worked example, using this job's numbers: to hold the start at the supply limit, the starter must bring a 45 A locked-rotor current down to 30 A, so terminal voltage must be 110 V × 30/45 ≈ 73 V, about 67% of nominal. At 67% voltage the locked-rotor torque is 0.67² ≈ 0.44 of its direct-on-line value. A single-phase capacitor-start compressor has a modest torque margin even at full voltage; asked to start against unequal refrigerant pressure with under half of it, it stalls.

A stall is worse than the peak it replaced, because the current sits near locked-rotor level for the whole ramp instead of collapsing within a fraction of a second. Compare winding heating, which scales as current squared times time, with example times: a direct start clearing in 0.5 s gives 45² × 0.5 ≈ 1,000 A²s; a 2 s ramp held at the limit gives 30² × 2 = 1,800 A²s, nearly twice the heat in the winding. The same trade appears when setting a soft starter current limit without overheating the motor, and the same torque deficit is why a single-phase soft starter can't fix a heavy fan start.

The setting follows from the arithmetic: start from the highest initial voltage the supply tolerates and keep the ramp at the short end. A limit deep enough to flatter the supply is deep enough to stall the compressor.

Verify the catalog model before the amps #

The proposal names ATS01N125FT, a 25 A unit. Its phase configuration is given inconsistently, described as single-phase in one place and as a three-phase model in another, so the manufacturer's datasheet and wiring diagram for that exact catalog number decide. If it is a three-phase model, it cannot start this compressor at any setting, and the question is closed.

ATS01N106FT is documented as a soft starter for asynchronous motors rated 6 A over 110 to 480 V, covering 0.75 to 3 kW, the right current class for this running current. Before selecting it, confirm from its documentation that single-phase compressor duty is permitted, which motor types it accepts (a permanent-split-capacitor motor and a capacitor-start motor with its relay are not the same load to the power semiconductors), and what starting duty the rating assumes.

Also establish how the unit controls the start. A voltage ramp alone raises terminal voltage on a timer whatever the current does, so a stalled compressor draws locked-rotor current for the full ramp; a current ceiling trims voltage to hold a set limit, at the cost of still more torque. Where a unit's label current and its power structure disagree, the check in matching a soft starter current range to its power structure applies.

De-energize the circuit, lock it out and test for absence of voltage before opening the compressor terminal box or the control enclosure to inspect the capacitor and relay wiring.

Restart delay lets the pressures equalize #

A refrigeration compressor starts against the pressure difference between discharge and suction. On a capillary-tube system, refrigerant bleeds back through the tube while the compressor stands and the pressures equalize, in small freezers typically within about five minutes, so the appliance's specified restart delay is the value to keep, and where none is published a short-cycle guard on that order is the setting. Verify the guard survives any thermostat or control replacement; a control that restarts on demand is how a healthy freezer starts tripping.

A thermostatic expansion valve or a liquid-line solenoid can hold the difference indefinitely; there the control sequence must let pressure equalize before the start, or the start stays hard no matter which starter is fitted. Small hermetic compressors carry an internal protector, a bimetal device that opens the circuit on a stalled start. It protects the winding, but every opening records a failed start; repeated openings mean the starting condition is wrong, not that the protection is working for you. Leave the refrigeration circuit alone: an improvised bypass is a performance and safety change that belongs to the refrigeration manufacturer or a qualified technician.

The decision, case by case #

Capillary-tube freezer, nameplate running current at or below 6 A, single-phase model confirmed. Select that current class, the documented ATS01N106FT where its manual confirms single-phase compressor duty and your motor type. Set the initial voltage as high as the supply tolerates, keep the ramp short, keep the restart delay at the appliance's value, then prove it with a measurement: the current should fall to running level within about a second and the terminal voltage should sag no more than the supply can stand.

Nameplate running current in the class above, up to 25 A. Take the next single-phase size. The proposed ATS01N125FT belongs here only if its datasheet documents it as a single-phase model; otherwise choose a single-phase unit in that class and apply the same three checks: phase, motor type, starting duty.

Trips persist with a correct delay, or the circuit holds pressure with a TXV or solenoid. The starter is not the fix. Correct the equalization delay and the control sequence first, because no setting creates the missing torque margin. If the load genuinely needs both a soft start and full starting torque, the clean route is a three-phase compressor motor fed from a drive rated for the single-phase supply; the sizing path is in sizing a VFD for a three-phase motor on single-phase input.

In every case the order holds: nameplate current for the class, documented duty and motor type for the model, restart delay for the start itself.

Questions asked

Will a bigger soft starter stop the compressor's internal overload from opening?

No. The protector inside a small hermetic compressor responds to winding heat, and a stalled start keeps the current near locked-rotor level for the whole ramp whatever the starter's rating. If it opens during a soft start, raise the starter's initial voltage, shorten the ramp, or lengthen the off-time so pressure equalizes. Upsizing the starter changes none of those three.

How do I tell a weak supply from a torque problem during a start?

Record current and terminal voltage together with a true-RMS clamp meter that captures inrush. If the current climbs while the voltage at the compressor terminals sags, the source is current-limited and a softer start helps. If the voltage holds near nominal while the current sits at locked-rotor level for a second or more, the rotor is not accelerating: the problem is torque or pressure, and a deeper ramp makes it worse.

Is a voltage ramp the same thing as a current limit?

No. A voltage ramp raises terminal voltage over a set time whatever the current does, so a stalled motor draws near locked-rotor current for the entire ramp. A current limit holds the current at a ceiling by trimming voltage, which cuts torque further; on a compressor the ceiling often has to sit near the locked-rotor current to keep the start moving at all.

Can a hard-start kit restore the torque a soft starter removes?

A start capacitor and relay raise locked-rotor torque on a direct-on-line start, but they work against the soft starter's reduced voltage, and whether a given starter tolerates a capacitor-switching relay in its circuit is a documented compatibility question. Check the starter manual's permitted motor types before combining them; if it excludes capacitor-start circuits, the pair cannot be used.

Keep reading

  • How-to

    Choosing a start capacitor for a 1/4 HP 120 V motor rewind

    Install 160 µF, inside the 100-200 µF range for this size, as the start capacitor on the 56-turn, 22 AWG start winding of a 1/4 HP, 4-pole motor, then verify by measuring start current and switch opening. The winding impedance, not the horsepower, fixes the value.

    Motors and motor starters

  • Explainer

    Converting a 350 kVA soft start limit to starting current

    A 350 kVA soft start limit is about 421 A of line current at 480 V: divide 350,000 VA by √3 × 480 V. The figure is apparent power, so no power factor enters the conversion, and it carries no duration — that comes from the torque-speed margin. The 12.5 kV fuse is a coordination problem; motor protection belongs at 480 V.

    Motors and motor starters

  • Troubleshooting

    Fixing a soft starter phase loss fault after a voltage change

    Set the soft starter's mains voltage parameter to 400 V and its motor rated current to the pump's 400 V nameplate value. The phase-loss monitor compares each phase with the programmed reference; at 400 V on a 690 V setting every phase reads about 42% low, past the documented 15% drop threshold, so the starter trips loss of phase even with all phases present.

    Motors and motor starters