Current IntelPower LibraryShop main store

Troubleshooting

Telling T6 from T9 when both leads carry the same tape

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

T6 and T9 are not interchangeable. Isolate all nine leads and measure: the lead that conducts to T3 is T6; the lead that conducts to T7 and T8 through the internal wye point is T9. One continuity check can pick the wrong lead, so take the full lead-to-lead matrix before reconnecting for 208 V.

On this page
  1. What T6 and T9 do inside the winding
  2. Isolate the leads before you measure
  3. Take the full matrix, not one beep
  4. The field check that points backwards
  5. Reconnecting the motor for 208 V
  6. The 208 V supply, by the numbers
  7. Verify before and after energizing
  8. Questions asked

No, they are not interchangeable, and with two leads wearing the same T6 tape you identify them with the winding itself, not the label. In a nine-lead dual-voltage motor, T6 is the far end of the T3 coil and reads low resistance to T3 only; T9 runs into the internal wye point and reads low resistance to T7 and T8. That difference survives any amount of bad tape. Isolate every lead, take the full lead-to-lead matrix, and let the topology name the leads before you make the 208 V splices.

What T6 and T9 do inside the winding #

A nine-lead dual-voltage wye motor has two coils per phase. The inner coil ends T10, T11 and T12 are tied together inside the motor as the wye point, and the T7, T8 and T9 coils each run to that point. The T4, T5 and T6 leads are the far ends of the T1, T2 and T3 coils, with no internal link to the wye point. That single difference in topology is your identifier:

Lead Internal path Reads low resistance to Reads open to
T6 Far end of the T3 coil T3 (one coil) T7, T8, T9 and the frame
T9 Coil end into the internal wye point T7 and T8 (two coils in series through the point) T3

The same discriminator holds on a nine-lead delta motor: there T6 completes the T3-T6 coil and T9 is an internal delta junction that conducts to T7 and T8. So the identification below stands either way; only the reconnection diagram changes, and a later section gives both.

Isolate the leads before you measure #

  • Lock out and tag the supply, then confirm zero volts at the motor terminals with a meter rated for the circuit. Open the conduit box only after that reading.
  • Photograph the existing 460 V connections and every lead marking before you disturb anything.
  • Pull apart the splice first that joins the two candidates together, because at 460 V the T6 and T9 ends are tied in the wye connection.
  • Separate every lead so no lead touches another, and tag the two duplicate leads A and B with fresh tape so the original markings cannot mislead you.
  • Count the leads. Nine numbered leads means this procedure applies. Twelve means a different winding with every coil end brought out; identify those by continuity across twelve-lead winding pairs, not by a wye-point test.
  • If more than these two markings are suspect, the wider procedure for identifying mislabeled leads on a nine-lead motor covers the full lead set.

Do not go on to measurements until no lead contacts another and every lead is individually tagged. A stray splice gives false continuity, and that is the most common way this test goes wrong.

Take the full matrix, not one beep #

Use the low-ohms range of a DMM or a milliohm meter. A motor coil reads small: continuity in ohms, often under 10 ohms on a machine this size, so a range that only resolves hundreds of ohms will call a good coil a short. Measure each candidate against the known-good leads and record every value:

Measurement If the lead is T6 If the lead is T9
Candidate to T3 Low resistance, one coil Open
Candidate to T7 or T8 Open Low resistance, two coils in series
Candidate to frame Open Open (a reading here is a ground fault, not an identifier)

Then cross-check with the coil values themselves. The T6-to-T3 reading should match what T1 gives to T4 and what T2 gives to T5, because all three are the same kind of coil. If the three readings disagree, you have picked the wrong lead or the winding has a fault; either way, stop and recheck before making any splice. When exactly one candidate conducts to T3 and the other conducts to T7 and T8, re-tape them as T6 and T9 and mark the numbers on the insulation itself, not only on tape.

The field check that points backwards #

You may hear a tip to measure from T3 to each candidate and call the one that beeps the real T9. Run that against the winding path above and it inverts: T3 shares a coil with T6, so the lead that conducts to T3 is T6, and the true T9 reads open to T3. One continuity check also passes with the wrong lead whenever the candidates were not fully separated. Take the matrix and let the topology decide; no single beep carries the identification.

Reconnecting the motor for 208 V #

The dual-voltage diagram on the nameplate is the authority, and for a standard nine-lead wye the low-voltage connection puts the two coils of each phase in parallel:

  • L1 to T1 and T7 joined.
  • L2 to T2 and T8 joined.
  • L3 to T3 and T9 joined.
  • T4, T5 and T6 tied together as the external star point.

If the nameplate shows a delta at both voltages, the groups are L1 = T1, T6, T7; L2 = T2, T4, T8; L3 = T3, T5, T9. Either way, this is why the two leads cannot trade places: T6 and T9 land in different phase groups, and swapping them puts a coil on the wrong phase, which unbalances the line currents and overheats one winding. For a motor with no usable markings at all, the method is the same one walked through in identifying unmarked nine-lead motor leads and wiring for 240 V. Before closing the box, ohm across the three line groups: each pair of groups should read the same value as every other pair, and each group should read open to the frame.

The 208 V supply, by the numbers #

The low-voltage rating on the nameplate is almost always 230 V, and 208 V is below it. The deviation is (230 − 208) / 230 × 100 = 9.6 percent low. NEMA MG-1, 2021 edition, covers motors and generators and allows operation at rated frequency with supply voltage within plus or minus 10 percent of rating, so this supply is inside the band but sitting on its edge: expect current to run high for a given load and temperature to follow. That reaches your protection directly. For a 7.5 hp example motor, NFPA 70, the National Electrical Code, 2023 edition, Table 430.250 lists 22 A at 230 V against 11 A at 460 V, and the overload setting follows the nameplate low-voltage amps under the nameplate-based rule in 430.32. Leaving the 460 V heaters in place is exactly how 460 V overload heaters fail a 208 V motor conversion; reset the overload to the low-voltage nameplate amps and confirm the requirement with your local authority having jurisdiction and the motor documentation.

Verify before and after energizing #

  • Megohm-test each lead group to the frame before energizing, at a test voltage appropriate to the winding rating. An insulation tester reads insulation integrity in megohms; it is not the tool for the coil matrix, and not all of them have a continuity mode.
  • With the splices made, recheck that the three line groups read equal to one another and open to the frame.
  • Measure the supply at the starter: about 208 V line to line, balanced on all three pairs.
  • Bump the motor unloaded and confirm rotation matches the arrow on the compressor. If it is reversed, swap any two line leads at the starter, never inside the motor box.
  • Clamp each line lead under load. The three currents should be balanced and below the nameplate low-voltage full-load amps. A large imbalance after a rewire points straight back at a swapped or misidentified lead, and a T6/T9 swap is the first suspect.

Questions asked

Both candidate leads beep to T7 and T8. What does that mean?

There is only one T9, so both cannot pass that test on a healthy isolated winding. Either a splice was left in place so the two candidates are still tied to each other, or the winding has a fault between coils. Go back, confirm every lead is separated with no contact, and retake the matrix before concluding anything about the motor.

My meter only beeps continuity and does not read ohms. Is that enough?

It is enough for the open-versus-closed matrix, because the identification depends on which pairs conduct, not on the exact value. The coil-resistance cross-check that confirms the choice needs a real low-ohms reading, so a meter with a low-resistance range or a milliohm meter is worth borrowing for that step.

Can I swap T6 and T9, bump the motor, and pick whichever way sounds better?

No. With one coil on the wrong phase group the three phases see different impedances, so current piles into one winding even unloaded. The motor may spin and sound almost normal while a winding cooks. Identify the leads by meter first; energizing is the last check, never the identification method.

Does this test work on a twelve-lead dual-voltage motor?

Not as written. A twelve-lead motor brings out every coil end, so there is no internal wye point and no lead that conducts to two others through it. You identify those leads by continuity pairs, because each numbered lead reads low resistance to exactly one partner, then group the pairs by phase.

Keep reading

  • How-to

    Reconnecting a 12-lead 575 V delta motor to 480 V wye

    Reconnection follows the standard 12-lead map whether the winding is concentric or lap: jumpers 4-7, 5-8 and 6-9 come off, leads 4, 5, 6, 10, 11 and 12 tie into one star point, and pairs 1-7, 2-8 and 3-9 land on the lines. Series delta at 575 V puts 287.5 V on each group; parallel wye at 480 V puts 277 V, about 3.6 percent low. Make the move only when the nameplate lists the wye connection at the new voltage.

    Motors and motor starters

  • Explainer

    What six leads and two plate voltages tell you about wiring

    Six leads are the two ends of three stator windings. Measure the supply, match it to a plate voltage line, and connect exactly as the plate diagram shows: wye ties the three winding ends together and lands supply on the starts, delta ties each end to the next start. A six-lead wye/delta pair sits 1.732 apart; a 230/460 pair means the plate diagram, not a rule, decides.

    Motors and motor starters

  • How-to

    Identifying leads on a six-wire two-speed single-phase motor

    No standard assigns colors to U, Um, V, Vm, W and Wm on a two-speed single-phase motor; the machine's winding diagram and rotary-switch contact schedule are the only authority. Map the six leads de-energized with an ohmmeter, land them per the schedule, and fit the specified run capacitor — 30 µF on the 230 V motor recorded here, where a 40 µF substitute ran rough on low speed.

    Motors and motor starters

Which wire is which on a seven-wire submersible pump motor