Why a low current limit stalls a soft starter start

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

A current limit set too low pins motor current at the ceiling while torque, which falls with the square of current, drops below what the load needs, so the motor stalls at that speed and heats until the overload, PTC or locked-rotor protection trips. Raise the limit to the lowest multiple of full-load current that reaches full speed with no flat plateau; use torque control on pumps.

On this page
  1. Torque falls with the square of the current
  2. Read the event log before changing a setting
  3. Worked example: a 100 A pump motor held to 2 x Ie
  4. Retune the start: limit, torque control, kick start
  5. Confirm the fix on the analog output
  6. Questions asked

A soft starter start that climbs part way, sits with the current pinned at the ceiling and ends in an overload, PTC or locked-rotor trip is a torque problem, and the current limit setting is usually the cause. On an ABB PST(B) softstarter the limit is adjustable from 1.5 to 7 times the set motor current Ie, and it works by capping the voltage the motor sees during the ramp; motor torque falls roughly with the square of that current, so a limit set low leaves only a small fraction of the direct-on-line torque. Wherever the load's torque demand crosses that fraction, the rotor stops accelerating at that speed, heats at the limited current, and a protection acts. Read the event log first, work the stall point with real numbers, then raise the limit to the lowest value that finishes the start.

Torque falls with the square of the current #

A phase-angle softstarter starts the motor by holding the voltage back, and the current limit is the ceiling on how far current, and with it voltage, may rise during the ramp. In the accelerating range, motor torque at any given speed follows the applied voltage squared while current follows the voltage, so torque falls roughly with the square of the current the limit allows. That gives the working rule, at every speed from zero to full:

available torque at a speed = direct-on-line torque at that speed x (limit current / direct-on-line current at that speed) squared

The load has its own demand at every speed. A centrifugal pump or a fan asks little at breakaway and most of its torque near full speed, so a limit that clears breakaway easily can still be crossed by the load curve somewhere in the top third of the ramp. When demand catches available torque, acceleration reaches zero: the rotor freezes at that speed, the unit holds current at the limit, and the winding dissipates heat in proportion to current squared for as long as the plateau lasts. Why a large motor stalls when the soft starter hits current limit describes the same plateau from the other side; there the ceiling is a supply or sizing constraint, here it is a setting you own and can raise.

Read the event log before changing a setting #

The PST(B) event log time-stamps every trip and pre-warning and names the protection that acted. Read it before touching a number, because the protections split into two families with different meanings:

  • Thermal — the dual motor overload model, selectable as classes 10A, 10, 20 and 30, and the PTC input. A thermal trip follows a long plateau: the overload model integrates heating, current squared over time, and the PTC reports actual winding temperature. Trips that arrive late in the ramp, and sooner when starts repeat, are accumulated heat.
  • Logic — locked rotor and underload. Locked rotor acts when current stays high while speed does not change: a jammed impeller or a seized bearing, rarely a setting. Underload acts on running current below the adaptable threshold, which points to a dry-running or closed-in pump and has nothing to do with the start. Confirm a mechanical jam with the starter locked out and absence of voltage verified at the motor terminals before putting a hand on the shaft.

The class numbers come from IEC 60947-4-1, the product standard for contactors and motor starters: a class is the maximum cold trip time in seconds at 7.2 times the set current, so a class 10 element must trip within 10 seconds at that multiple and a class 30 element within 30 seconds. A stalled start pinned at two to three times set current accumulates heat far more slowly than that, which is why the plateau can hold for tens of seconds before the overload acts — the plateau is the symptom, the trip is only the ending. Confirm the class choice against the motor manufacturer's thermal data and the starter's own documentation.

Worked example: a 100 A pump motor held to 2 x Ie #

Take a typical case; every value below is an example, and the real ones come off your motor's data sheet and the pump curve.

The inputs:

  • Motor: three-phase induction, 400 V line-to-line, 50 Hz, nameplate full-load current Ie = 100 A.
  • Starter: current limit set to 2 x Ie, inside the documented 1.5 to 7 x Ie range but low for this duty.
  • Direct-on-line accelerating current: about 6 x Ie, typical of a standard-design motor; read your machine's own figure, since the range the standard actually permits is explained in what IEC 60034-12 actually limits on motor starting current.
  • Load: a centrifugal pump, whose torque demand rises with speed squared, so at 85% speed it needs about 0.85 squared, call it 0.7, times rated torque.
  • Motor torque: 2.0 times rated torque available direct-on-line at 85% speed, an illustrative value approaching breakdown; your curve decides the real number.

The rule in words: multiply the direct-on-line torque at each speed by the square of the ratio of limited current to direct-on-line current, and compare the result with the load's demand at that speed.

The arithmetic:

  • Limit current: 2 x 100 A = 200 A. Direct-on-line current: 6 x 100 A = 600 A.
  • Current ratio: 200 A / 600 A = 0.33, and 0.33 x 0.33 = 0.11.
  • Available torque at 85% speed: 0.11 x 2.0 = 0.22 times rated torque, against a demand of 0.7 times rated. 0.22 sits far below 0.7, so the rotor freezes near 85% speed with current pinned at 200 A and heating climbing at the square of that current.
  • The same ratio against a locked-rotor torque of roughly one-and-a-half times rated leaves about 0.17 times rated at breakaway — enough for a pump, which is why the start clears breakaway and dies high in the ramp.

Solving for the limit that clears the demand: (I / 6) squared, times the 2.0 torque figure, must reach 0.7; so (I / 6) squared reaches 0.35, I / 6 reaches the square root of 0.35, about 0.59, and I reaches 6 x 0.59, about 3.5 x Ie.

The result: about 3.5 x Ie is the floor for this example load. The decision: set the next practical step, 4 x Ie = 400 A, and check it the same way — 400 A / 600 A = 0.67, squared about 0.44, times 2.0 gives 0.89 times rated torque, above the 0.7 demand with margin. The square-law is an approximation and both curve values are illustrative, so treat the computed floor as where the search begins; the answer is the lowest setting that completes the real start on the process load.

Retune the start: limit, torque control, kick start #

Work the sequence in order and stop when the trace is clean:

  1. Record every present setting from the full-text display menu before changing anything: rated motor current, current limit, overload class, ramp time, kick start.
  2. Clear the mechanics first. A jammed impeller, a closed discharge valve or a dry suction stalls any limit; locked rotor and underload protection exist for exactly those conditions, so let them report rather than disabling them.
  3. Check the current base. In inside-delta connection the softstarter carries winding current, which is line current divided by the square root of three; that is why the series is rated 30 to 1050 A in line and up to 1810 A inside delta (1050 x 1.732 = 1819, published as 1810 A). Set the rated motor current to match the connection, or the limit and the overload model both work from the wrong base.
  4. Raise the limit in steps across the 1.5 to 7 x Ie range and stop at the lowest setting that reaches full speed on the process load with no flat plateau. Take the manufacturer's application table as the floor — the softstarter handbook, for instance, lists 3.5 x Ie for compressors — not a guess from further down. A longer ramp time only stretches the plateau; it never moves the stall speed. The detail behind this step is in Setting a soft starter current limit without overheating the motor.
  5. For pumps, replace the flat current ceiling with torque control, which shapes torque along the ramp the way the load wants it; Which soft starter control mode fits each load type maps each mode to its duty.
  6. Reserve kick start for genuine breakaway jams, at the minimum pulse that frees the load, not as a permanent patch on every start.
  7. Match the overload class, 10A, 10, 20 or 30 on this range, to the motor's thermal capability and the measured start duration, then leave it; lengthening the class so a stalled start stops tripping only moves the same heat into the winding with less margin. How the rotary-switch ranges pair FLC and trip class walks through that pairing.

Confirm the fix on the analog output #

Program the analog output, selectable 0-10 V, 0-20 mA or 4-20 mA, to report current and capture a full start on a chart recorder, a PLC analog input, or a fanless mini PC that logs the trend. Do any terminal work at the starter with the panel locked out. A corrected trace shows:

  • current rising to the set limit, then falling away as speed builds, with no extended plateau;
  • the peak held at or below the limit, with a supply voltage dip the rest of the panel tolerates;
  • a start time comfortably inside what the selected class allows at that current;
  • full speed reached with the process connected, not on a motor-alone test;
  • repeated starts at the plant's real duty producing no pre-warning, and an event log that stays empty afterwards.

One running note: if the start is now clean but the enclosure runs hot at full speed, that is a separate loss, because with no bypass the thyristors conduct the entire time the motor turns. Sizes from 370 A up in the PSTB carry a built-in bypass contactor, and the smaller PST sizes, 30 to 300 A, are prepared for an external bypass, which is the fix for running heat.

Questions asked

What does the kick start pulse do on a jammed pump?

The pulse applies its own boost level for its set duration, breaking the load free, then the ramp resumes under the normal current limit. Keep both values at the minimum that frees the impeller, and once the jam is cleared, test whether the plain ramp completes without the pulse. A start that only passes with a kick every time still has a torque deficit to fix.

Why does the same start pass cold but trip when repeated?

The electronic overload model carries thermal memory between starts, and the PTC sensors report real winding temperature, so back-to-back starts stack heat even when each ramp looks identical on the trace. Give the motor the cooling interval the manufacturer states between consecutive starts; if the duty truly needs more starts than that, the limit is too low or the class too short for the job.

Can the underload protection double as a dry-run guard after the start is fixed?

Yes. Once the motor reaches full speed reliably, set the underload threshold from the pump's normal running current at process flow, with enough margin that a closed suction or a lost prime drops below it while normal load swings do not. Route the trip to a stop or an alarm instead of disabling it; a dry pump destroys seals quickly.

Does a stalled start hurt anything besides the motor?

It holds elevated current for the whole plateau instead of the second or so a healthy inrush lasts, so the voltage dip persists across the supply for that time and anything sharing the feeder sees it. Contactors can drop out on a deep dip, and on a generator the prime mover's own limits may end the attempt before your overload does.

Keep reading

  • Troubleshooting

    Diagnosing a soft starter fault or alarm before resetting it

    Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.

    Motors and motor starters

  • How-to

    Setting a soft starter current limit without overheating the motor

    Set the soft starter current limit from the accelerating torque the load needs, not from the starter's duty figure. Estimate the limit as locked-rotor current times the square root of required torque over locked-rotor torque, check that current, dwell time and starts per hour against the starter's duty table, then verify every start with a measured peak current and acceleration time. At a 300% limit a typical design B motor develops only about a third of its full-load torque.

    Motors and motor starters

  • Troubleshooting

    Why a large motor stalls when the soft starter hits current limit

    Log shaft speed against current at the stall. A reading near 214 rpm (one-seventh of the 1500 rpm synchronous speed) or 115 rpm (one-thirteenth), with 3-4 current-envelope teeth per second at the 1809.5 A limit, is induction-motor crawling aggravated by SCR harmonics, not a rotor fault. Raise the current limit and shorten the dwell; the paralleled transformers made it worse by stiffening the source.

    Motors and motor starters