Troubleshooting
Why a soft starter overload trip during start means a stalled motor
Short answer
An overload trip 30 to 40 seconds into a soft-started pump run is not a nuisance trip: the starter held its current limit while the motor failed to reach speed, and the electronic thermal model integrated several times rated current until it tripped. Read the fault history, correct the entered motor current and trip class, clear the load-side drag, then raise the starting voltage in steps until current falls off the limit before the ramp ends.

On this page
- A start pinned at the current limit is a stalled motor
- What the pump row's suggested values mean
- Read the fault history before changing anything
- The two settings the trip depends on
- Find the load-side torque the start cannot deliver
- Fix it in this order
- Verify the next start from cold
- The decision
- Questions asked
An overload trip that lands 30 to 40 s after the on command is almost never a nuisance trip. The starter is doing what it was set up to do: it ramps motor voltage until the current reaches the set limit, then holds the current there. When the torque available at that limited current cannot accelerate the pump, the rotor stays near standstill while the electronic overload model integrates several times the motor's rated current, and it trips when the stored heat reaches the class limit. Run the checks below in the order given; do not move past a step until its expected reading comes back true.
A start pinned at the current limit is a stalled motor #
During the ramp the starter raises the motor voltage until current reaches the limit and then pins the current there. Near standstill, motor current falls roughly in proportion to voltage and torque falls roughly with the square of it, so the torque a struggling motor can develop is fixed by wherever that limit pins the voltage.
Worked example, with illustrative inputs only: a 250 kW, 400 V, 50 Hz three-phase pump motor with a 460 A nameplate current and a locked-rotor current of 6 × 460 A = 2760 A, started on the pump row's settings. The limit of 4 × Ie — Ie is the rated motor current entered as the overload setting — works out to 1840 A. Holding 1840 A on a motor that would draw 2760 A at full voltage puts the terminal voltage near 1840 ÷ 2760 ≈ 0.67 of rated, about 267 V, and the torque available there is roughly (267 ÷ 400)² ≈ 0.44 of the full-voltage locked-rotor torque. If the pump needs more than that to break away and accelerate, the rotor sits still while the starter holds the limit.
The thermal model stores heat in proportion to current squared, so at that limit it accumulates about (4 ÷ 7.2)² ≈ 31 % of the heat per second that drives a Class 10 trip at its 7.2 × Ie reference point. That is why a stalled start trips in the tens of seconds rather than at the class time, and why a start that truly completes never trips: running current alone does not fill the model. Every number in the example is an estimate from the stated inputs; the real trip time follows the thermal model documented for the starter. Trip classes are defined in the IEC 60947 product standards for motor-control gear, and the classes your starter offers are listed in its manual. This is the same mechanism that makes a large motor stall when the soft starter hits current limit.
What the pump row's suggested values mean #
The application table published for this starter family packs four settings into one row per duty. The pump row reads:
| Setting | Pump row value |
|---|---|
| Starting voltage | 40 % |
| Ramp-up time | 3 s |
| Current limitation | 4 × Ie |
| Stopping time | 10 s |
The row carries a footnote marker; read that footnote in the SIRIUS 3RW50 equipment manual, document ID 109753750, before commissioning, because it qualifies the values. They are suggestions for a pump that can accelerate freely, not guaranteed settings: at 40 % voltage the torque is only about 0.40² = 16 % of the full-voltage value at the same speed, so a closed check valve, static head or a stiff bearing easily exceeds it. Read the live starting voltage, ramp time and current limit back from the device's parameter menu; what the unit actually holds matters more than what was last written into it.
Read the fault history before changing anything #
Assign no cause before you have read the message the starter itself raised:
- Open the fault and event history on the starter's display or in the commissioning software and copy the exact message text.
- Check that text against the fault table in the 3RW50 equipment manual before calling it a motor overload.
- Separate a motor overload message from a device overtemperature message. Heat-sink trips point at starts per hour, ambient temperature, ventilation clearance or a bypass that never closed, and their corrections have nothing to do with start torque.
Expected reading: a motor overload message. If the history is ambiguous or the alarm text does not match an obvious cause, work through diagnosing a soft starter fault or alarm before resetting it, then return to the steps here.
The two settings the trip depends on #
The entered motor current. The overload model is only as accurate as this entry. If it sits below the nameplate full-load current at the supply voltage actually in use, the model runs hot at ordinary load and trips early, and because the limit is a multiple of Ie the same error shrinks the limit in amps and starves the start of torque. If the motor is connected inside the delta, the entry convention differs from a line connection; follow the manual.
The trip class. A heavier class only delays the trip; it creates no torque. Select the class for a pump with a long but real acceleration, and treat any class change as temporary until the stall itself is fixed. Reading overload relay trip classes and curves shows how a class number converts into trip times.
Expected reading: the entered current equals the nameplate value for the real connection, and the limit that follows from it sits inside the rated range of the starter, the motor and its feeder. The manual caps the limit setting at the position marked max., equal to 7 × the starter's maximum rated operational current; that cap is not permission to exceed the motor's or the cable's ratings.
Find the load-side torque the start cannot deliver #
No setting fixes a load that needs more torque than the motor can produce at the limited voltage. De-energize, lock out and verify absence of voltage before any hand-turn or inspection that opens the pump's terminal box or coupling guard. Then check:
- Start condition against pressure: a discharge valve left open, or a pump cranking against a closed-line check valve, raises breakaway and acceleration torque through the whole ramp. Throttle or bypass at start-up where the process allows.
- Rotation direction: a pump running backward against its design draws abnormal current; confirm the shaft against the rotation arrow at a brief supervised jog.
- Bearing, seal or coupling drag: a bound impeller or a seized bearing can exceed the torque at any voltage; turn the shaft by hand only with power locked out and absence of voltage verified.
- Supply voltage sag: torque falls with the square of voltage, so a feeder that sags during the start cuts torque hard; log the voltage at the starter terminals during a start.
- Phase imbalance or a loose lug: unequal phase currents mean extra heating and less torque; clamp all three phases during a start.
Expected reading: phase currents equal within a few percent, the current pinned at the limit only briefly, then falling toward running current as the pump accelerates. A current that stays pinned for the entire ramp means the load or the settings exceed the available torque.
Fix it in this order #
Change one setting at a time and let the motor cool between attempts; a stalled start leaves heat in the model that an alarm reset does not clear.
- Correct the entered motor current to the nameplate value for the real supply voltage and connection.
- Raise the starting voltage in steps above the 40 % row value until the shaft turns promptly as soon as the ramp begins.
- If the motor still stalls at the limit, raise the current limit in steps, inside the manual's range and the ratings of the motor and its feeder.
- Shorten the ramp time to the fastest value the pump still follows smoothly; a ramp the pump cannot follow at the available torque only extends the seconds spent at the limit.
- Repeat from cold after each change and compare the current trace, not just the trip.
Setting a soft starter current limit without overheating the motor walks through the tradeoff in step 3: a higher limit buys torque and spends motor heating, so raise it no further than the start actually needs.
Expected reading: the start completes in about the programmed ramp time and the current leaves the limit before the ramp ends.
Verify the next start from cold #
- Clamp all three phases and start from a cold motor: current rises to the limit, leaves it before the ramp ends, and settles below the nameplate current at normal pump load.
- Watch the status after the ramp: the starter should show run. If the ramp completes but the unit never shows run — a bypass that reports open at top of ramp is a switchover failure, not a stall — follow the procedure written for that fault instead of the steps here.
- Let the pump run several minutes: no overload alarm, and the thermal utilization reading, if displayed, stays well below the trip threshold.
- Make a second start within the manufacturer's permitted starts per hour: the same ramp time, the same current profile, no trip.
The decision #
- Current leaves the limit before the ramp ends and the alarm stays gone: the start was torque-starved at the suggested voltage, and the raised starting voltage, with the limit raised only if it was needed, is the fix.
- Current stays pinned for the whole ramp even after voltage and limit are raised: the load needs more torque than the motor delivers. Clear the mechanical cause, start the pump against a throttled discharge where the process allows, or accept that the motor and starter are undersized for this duty.
- The message is device overtemperature, not motor overload: correct the starts per hour, ambient, ventilation or bypass closure; the start settings are not the problem.
- The overload returns on every cold start with correct entered data and a free-turning load: suspect the motor itself, because a stator or rotor fault also cuts torque, and test the machine separately.
Questions asked
Why does the overload alarm come back right after a reset and restart?
A reset clears the alarm message, not the stored heat. An electronic thermal model keeps its accumulated value after acknowledgement, so a motor that stalled once reaches the trip point sooner on the next attempt. Let the motor cool until the model's utilization reading falls, and correct the starting voltage or current limit before restarting. The 3RW50 manual documents the RESET MODE setting that governs what the starter does after a fault acknowledgement.
Is the published pump row guaranteed to start every pump?
No. The row is a suggestion for a pump that can accelerate freely, and its footnote in the equipment manual qualifies it. A pump against a closed check valve, high static head or stiff bearings needs more breakaway torque than that row delivers, so treat the published voltage as the first step and raise it until the shaft turns promptly when the ramp begins.
When is an overload trip at start not a stalled motor?
When the message is device overtemperature rather than motor overload. A heat-sink trip points to starts per hour above the rating, high ambient temperature, blocked ventilation or a bypass that never closed, so the thyristors keep dissipating during the run. Read the exact message text in the fault history and check the fault table in the 3RW50 equipment manual before assigning a cause; the corrections differ completely from the stall fixes.
What does the trip class number actually set?
It sets the maximum cold trip time at 7.2 times the entered motor current. A Class 10 model trips within 10 seconds at that multiple, and heavier classes stretch the time for long-acceleration loads such as large fans. No class rescues a stalled start: the current stays at several times rated for as long as the rotor sits still, so every model trips eventually.