Troubleshooting
Why a VFD trips a motor overheat fault: causes and checks
Short answer
A motor overheat trip on a drive is either real heat — blocked cooling, a hot room, a heavy or binding load, low-speed running — or a false report from a broken sensor circuit or a motor-current entry that doesn't match the nameplate. Work from the motor's cooling and load to the thermistor or RTD path, then the drive's motor data, and fix the cause instead of raising the trip level.

On this page
- What the drive is actually reporting
- Real heat: check the motor and its cooling first
- Load and mechanics: heat without a jam
- Worked example: a 10.5 A nameplate against an 8.0 A drive entry
- The temperature-sensor path: real report or false one
- Motor data: where false trips hide
- Low-speed and high-speed running
- The decision for each case
- Questions asked
A motor overheat fault on a drive means one of two things: the windings really are too hot, or the protection path is reporting heat that is not there. The reliable order of work runs from the motor to the drive — cooling, then load, then the temperature-sensor circuit, then the drive's motor data — and you fix the cause you find instead of raising a trip level. Real heat comes from blocked cooling, a hot room, a binding load, continuous low-speed running without forced air, or damaged windings. A false report comes from an open or shorted sensor circuit, a sensor input configured for the wrong device, or a motor-current entry that does not match the nameplate. The fault table in your drive's manual tells you which element tripped, and that decides where you start.
What the drive is actually reporting #
Two different elements can raise a thermal flag, and they fail in different ways.
- A winding sensor. A PTC thermistor or an RTD embedded in the windings feeds an isolated sensor input on the drive. A PTC is a threshold device: below its trip temperature it reads as a healthy low-resistance circuit, and at its trip temperature the resistance climbs steeply, which the drive reads as overtemperature. An RTD reports a resistance the drive converts into a temperature it can display and trend. When this path trips, most drives show a dedicated overtemperature code.
- The drive's thermal model. The drive measures its own output current, divides it by the motor rated current entered in the parameters, and accumulates a heating estimate against a pickup at that same setting. Depending on the manufacturer, its trip is shown as a motor overload code rather than an overheat one; why a VFD reports a motor overload fault covers that trip's own causes.
Record the displayed temperature or sensor state, the output current, the load and the ambient before you reset, so you can tell later whether the indication moved with reality.
Real heat: check the motor and its cooling first #
Most trips on motors that have run fine for years start here.
- With the motor running, look first: shaft fan turning, air moving through the fins, guards and inlets clear of dust and wrapping.
- De-energize, lock out and verify the absence of voltage before you open the motor terminal box or any drive cover; NFPA 70E, 2024 edition, governs the approach, the absence-of-voltage test and the protective equipment for that work, so follow your site's procedure and confirm the details with your authority having jurisdiction.
- Clean blocked fins, vents and fan guards, and confirm the fan turns freely in its intended direction.
- Measure the ambient at the motor's air inlet during the hottest shift; most general-purpose industrial motors carry a 40 °C ambient rating, and the nameplate or the motor documentation states the actual limit for yours.
- Trend frame temperature at the same spot each check with an infrared thermometer; a surface reading sits below the winding temperature, so the trend and a comparison with a healthy twin motor matter more than any single number.
- After restoring the cooling path, run the machine under observation and confirm the indication stabilizes instead of climbing cycle after cycle.
Load and mechanics: heat without a jam #
Excess torque demand becomes excess current, and excess current becomes heat whether or not anything looks jammed.
- Compare the drive's displayed output current with the nameplate full-load current across a complete production cycle, not a snapshot.
- Inspect the driven machine for blockage, overfeed and stiff spots, and check the coupling alignment.
- Check the bearings: noise, vibration or a local hot spot at the bearing housing all add friction load.
- Watch the duty cycle: a temperature that climbs across repeated start-stop or heavy-load cycles means the motor is not getting enough time to shed heat between them.
- Unequal current among the three output phases adds heating without tripping anything on its own; the routine in what to measure when a VFD trips a motor phase loss fault is the way to take that measurement.
If the process legitimately demands more than the motor's rating, that is a sizing problem, and no setting makes it otherwise.
Worked example: a 10.5 A nameplate against an 8.0 A drive entry #
The inputs below are illustrative example values of the kind you read off a nameplate and a keypad — no specific drive or motor is implied.
- Motor nameplate full-load current: 10.5 A, three-phase, 460 V, 60 Hz.
- Motor rated current entered in the drive: 8.0 A, left over from the smaller motor it replaced.
- Drive's displayed output current at the observed load: 10.2 A, the average of the three output phases.
The rule: the drive's thermal model divides measured current by the motor rated current it was given and accumulates an I²t heating estimate against a pickup at that same setting, so what it acts on is the ratio of those two currents. The code anchor is NFPA 70, the National Electrical Code, 2023 edition, section 430.32(A)(1): a separate overload device on a motor rated more than 1 hp trips at no more than 125% of nameplate full-load current when the service factor is 1.15 or higher, and no more than 115% otherwise. Article 430's adjustable-speed-drive provisions let the drive's electronic overload serve as the motor's overload protection; confirm the section, your edition's local amendments and the arrangement with your authority having jurisdiction.
The arithmetic:
- What the model sees: 10.2 A ÷ 8.0 A = 1.275. The drive believes the motor is running at 128% of its rating, a sustained level that accumulates to a trip.
- The permitted ceiling applied to the wrong entry: 1.25 × 8.0 A = 10.0 A. Even at the maximum allowed trip level, the drive would trip below the motor's true 10.5 A rating.
- With the correct entry: 10.2 A ÷ 10.5 A = 0.971. The motor is actually at 97% of its nameplate rating, below any overload pickup.
A healthy motor at 97% of its real rating was presented to the model as a 128% load. The trip was false, and the cause was data, not heat.
The decision: enter 10.5 A — the nameplate figure — as the drive's motor rated current, leave the thermal protection enabled, reset and watch a full production cycle. If the fault still returns at or below 100% of the corrected setting, with clean cooling and a frame that is only warm, stop treating it as data and go back to the physical and sensor checks.
The temperature-sensor path: real report or false one #
A cool frame with a high or stuck indication convicts the sensor path; a hot frame with a smoothly rising, plausible indication convicts the physics.
- Identify the installed device from the motor documentation: a PTC switches at one preset temperature and behaves like a contact; an RTD gives the drive a temperature it can display and trend.
- Confirm the drive's sensor input is configured for the device actually installed, and that the sensor lands on the drive's dedicated sensor terminals; an RTD often needs those terminals or an option card the drive may not carry.
- With the motor isolated, measure the sensor circuit at the motor terminal box against the documented values for a new sensor of that type: a cold PTC circuit should read as a continuous low-resistance run, while an open conductor, a shorted pair or a grounded conductor reads wrong in its own way.
- Trace both conductors for damage and keep them out of the power cables' raceway. The drive's sensor input is isolated from its power circuits — IEC 61800-5-1, the safety standard for power drive systems (edition 3.0, 2017), sets the insulation requirements separating circuits above 50 V from low-voltage control and sensor circuits — and induced voltage on a shared run can hold the input tripped. Confirm the edition and the terminal assignments with the drive manual and your authority having jurisdiction.
- Trend the indication against an independent reading: an infrared thermometer on the frame will not match a winding number, but during warm-up and cool-down the two curves must move together. An indication that stays frozen while the frame cools is a failed sensor circuit.
Repair the path, then prove it with a plausible cold reading and a smooth rise on a controlled start. Never bypass the temperature protection to keep the line running; the repair is minutes of work, a cooked winding is a rewind.
Motor data: where false trips hide #
The motor rated current entry takes the nameplate's full-load current — not a fraction of it, not the drive's own rating. The reasoning is in why the VFD's motor overload current setting takes the nameplate FLA, and the worked example above showed what one stale entry does.
Two habits trip people up:
- Overload-relay practice does not transfer. The dial on a classic thermal overload relay scales within the relay's setting range; what the thermal overload relay current setting dial actually shifts explains that device, which is not the drive's model.
- If the nameplate is gone or painted over, calculate the current before entering anything; calculating nameplate full-load amps for a three-phase machine walks through what to read off the machine.
Log the original entry and the corrected one, with the reason, before restarting.
Low-speed and high-speed running #
A standard self-cooled motor depends on its shaft-mounted fan, and that fan slows with the motor. Continuous rated torque at low speed therefore heats windings that the same current at base speed would keep cool — a real overheat with correct data and a clean cooling path. The answers are mechanical or electrical, not settings: a separately ventilated motor or blower, a larger frame, or a duty limit at that speed. Above base frequency the picture inverts — the voltage stops rising with speed, torque falls away, and demanding rated torque there overheats the motor as well; why motors overheat when a VFD runs above base frequency works through that case.
The decision for each case #
- Cool motor, high or stuck indication → repair or replace the sensor circuit and configure the input for the installed device; never bypass the protection.
- Frame hot, output current at or below the nameplate rating, dirty cooling or a hot room → clean and restore the cooling path, fix ventilation, re-trend.
- Output current above the nameplate rating with binding, misalignment or bearing noise → fix the mechanical fault; if the load is genuinely larger than the motor, resize the motor.
- Temperature climbs across cycles → duty cycle; add cooling time or forced airflow.
- Trip cleared by the corrected motor rated current entry → leave the protection enabled at the nameplate value and log the change.
- Trip persists at or below 100% of the corrected setting, cooling clean, sensor healthy → suspect the windings; an insulation-resistance test at the voltage the motor documentation specifies, with the motor isolated, tells you whether the machine goes to a rewind shop.
Questions asked
How long should the motor cool before I reset the fault and restart?
Restart on the indication, not the clock. An RTD input falls smoothly as the windings cool; a PTC resets on its own once it drops below its trip temperature, and the drive then lets you clear the fault. Small frames shed heat in tens of minutes, larger ones take considerably longer, and a restart into a still-hot winding simply trips again. Confirm the displayed value has returned near its cold reading before you press reset.
Can the motor's thermistor leads run in the same conduit as the power cables?
No. The sensor conductors carry a small signal into an isolated low-voltage input, and the switching output cables around them induce voltage on every run. Keep the sensor wiring in its own conduit or a segregated compartment, cross power runs at right angles where you must pass them, and terminate at the drive's dedicated sensor terminals only. The drive manual states the allowed cable and routing; follow it.
The fault only appears on hot afternoons. What does that pattern tell me?
A fault that tracks the hottest part of the day points at lost thermal margin, not at a sensor fault: the same load sits closer to the limit when the air around the motor is hotter. Measure the ambient at the motor inlet on one of those afternoons and compare it with the ambient the nameplate allows, which is 40 °C on most general-purpose industrial motors. Shading, moving the heat source or adding airflow restores the margin.
The fault comes back seconds after reset. Does that rule anything out?
Speed of return is itself a clue. A temperature indication that falls normally, a PTC circuit that resets when cool, and then an instant re-trip points at the sensor wiring: a conductor rubbed through or a terminal moving with vibration trips regardless of how cold the motor is. A thermal-model trip that returns within seconds means the model never cooled below its pickup, which happens on repeated starts into a heavy load. A winding genuinely that hot usually shows other symptoms first.

