Explainer
Why busbar force depends on asymmetric fault current
Short answer
Busbar force varies with the square of the instantaneous fault current, so the asymmetric first-cycle peak sets the mechanical duty on switchgear bus, not the symmetrical RMS value a transformer-impedance study gives. Compare the computed peak against the assembly's documented peak withstand, and treat an application above the guide's X/R basis as special for the switchgear manufacturer.

On this page
If you take the mechanical check on a switchgear bus straight from the available symmetrical fault current, you will understate the worst load the bus ever sees. Busbar force grows with the square of the instantaneous current, and a fully offset first peak reaches about 2.6 times the symmetrical RMS value, so the force at that peak is roughly 3.4 times what a symmetrical-only calculation reports. What follows is the formula, a worked example on a bus faulted at 20 kA RMS, and the decision for each case you are likely to meet.
Which current bends the bus #
A short-circuit current is not one number. The symmetrical RMS value is the AC component alone: it is what the transformer impedance gives you at the secondary terminals, the same figure you get calculating transformer fault current from percent impedance at the terminals. Close a fault near a voltage zero and the circuit's inductance adds a decaying DC component on top. The sum, the asymmetric current, reaches its largest instantaneous value at about the first half-cycle, roughly 8.3 ms at 60 Hz, while most of the DC component is still present.
Force between two parallel conductors is proportional to the product of their instantaneous currents, so with equal and opposite current in the pair the force goes as the current squared. That square is what makes asymmetry expensive: the DC offset raises the first-cycle peak by a factor of about 1.83, and the force rises by the square of that. Two consequences follow. The worst mechanical load is a first-cycle event, finished before any breaker opens. And the X/R ratio at the fault (reactance over resistance, which sets how slowly the DC decays) matters as much as the fault magnitude, because the whole source path, not just the transformer, sets it; that is why calculating low-side fault current with source impedance changes both the current and the asymmetry you carry into the bus check.
When a generator dominates the source impedance, the AC component itself decays during the fault, the behaviour addressed when handling generator fault-current decay in arc-flash studies; the first-cycle peak factor below still applies at inception.
The force formula and the peak factor #
For two parallel conductors whose spacing is large compared with their dimensions, the force per unit length is F/l = μ0 · i² / (2π d), with μ0 = 4π×10⁻⁷ H/m, i the instantaneous current magnitude in amperes in each conductor of the pair, and d the centre-to-centre spacing in metres; the result is in newtons per metre. Since μ0/(2π) = 2×10⁻⁷, the working form is F/l = 2×10⁻⁷ × i² / d. Flat bars mounted close together need shape correction factors, which the manufacturers' design methods supply; the current relationship itself does not change.
The worst-case first-cycle peak, for a fully offset wave, is i_pk = √2 × I_sym × (1 + e^(−π/(X/R))). Evaluate that at X/R = 17, the application basis IEEE Std C37.010-2016 uses for AC high-voltage circuit breakers rated on a symmetrical-current basis, and the factor comes to about 2.6; above that ratio the same guide classes the application as special and to be reviewed with the manufacturer. C37.010 is an application guide rather than an installation code, so confirm how its basis applies to your assembly with the switchgear manufacturer's documentation and your authority having jurisdiction.
First-cycle force on a bus faulted at 20 kA RMS, X/R 17 #
The inputs, each with its source:
- Symmetrical RMS fault current at the bus: 20 kA. An illustrative study value typical of a metal-clad switchgear bus; your value comes from your own short-circuit study.
- X/R at the bus: 17, the C37.010 application basis, so the standard peak factor applies.
- Conductor spacing: 0.2 m centre-to-centre between adjacent phase bars. Illustrative geometry; read the real spacing from the switchgear drawings.
- Constants: √2 = 1.414 and μ0/(2π) = 2×10⁻⁷.
The rule in words: the first-cycle peak equals root-two times the symmetrical RMS current, times one plus e raised to minus pi over the X/R ratio; the force per metre between two adjacent bars is two times ten to the minus seven, times the square of that instantaneous current, divided by the spacing in metres.
The arithmetic:
- Peak factor: e^(−π/17) = e^(−0.185) = 0.831, so 1 + 0.831 = 1.831, and 1.414 × 1.831 = 2.59.
- First-cycle peak: 1.414 × 20,000 A × 1.831 ≈ 51,800 A, that is 51.8 kA.
- Force per metre, asymmetric basis: 2×10⁻⁷ × (51,800 A)² / 0.2 m = 2×10⁻⁷ × 2.683×10⁹ A² / 0.2 m = 536.6 / 0.2 ≈ 2,683 N/m.
- Symmetrical-only comparison: the study value times 1.414 is 28,280 A, and 2×10⁻⁷ × (28,280 A)² / 0.2 m = 2×10⁻⁷ × 7.998×10⁸ A² / 0.2 m ≈ 800 N/m.
Result: the fully offset first peak pulls adjacent bars with about 2,680 N per metre of run, roughly 3.4 times the 800 N/m a symmetrical-only check reports. This is the two-conductor first-pass figure: a real three-phase run sums contributions from both neighbouring phases, with bar shape and support layout on top, which is what the manufacturer's bus design method handles.
The decision: an assembly rated at this symmetrical current and this X/R basis is braced for exactly this peak, so the calculation confirms the rating rather than challenging it. If the documentation states a peak withstand or close-and-latch current, put the computed 51.8 kA against it directly. If your study's X/R is higher than the basis the rating was stated at, stop treating the worked factor as the ceiling and take the application to the switchgear manufacturer.
What the switchgear rating states, and how to compare #
Manufacturer ratings documentation defines the rated short-circuit withstand current of a switchgear bus as the rated symmetrical short-circuit current the bus must withstand for a stated time, and many assemblies state a peak capability alongside it, a peak withstand current or, on the breaker side, a close-and-latch current, precisely because the mechanical duty is a peak event. Compare like with like: the computed first-cycle peak goes against the peak figure, and the symmetrical study value with its duration goes against the withstand figure. It is the same bookkeeping that governs sizing low-voltage switchgear with RMS versus peak values for breaker selection, and mixing the two is the error that hides an understressed bus.
Physical verification of bus bracing, spacing or supports happens with the gear de-energized: lock out, test for absence of voltage on each phase, and work to NFPA 70E, 2024 edition, for approach boundaries and protective equipment. The calculation is desk work; the nameplate and the manufacturer's documentation state what the assembly is built to take.
The decision for each case #
- X/R at the bus is at or below the guide's basis, and inside the assembly's stated rating basis: compute the first-cycle peak force with the drawing's spacing and file it against the peak and withstand ratings. The symmetrical study value plus the documented basis covers the bus, and no special review is needed.
- X/R above the guide's basis, or the rating basis not documented: the peak factor exceeds the worked figure and the force grows as its square, and IEEE Std C37.010-2016 already classes the application as special, so get a configuration-specific determination from the switchgear manufacturer before relying on the bus.
- Computed duty exceeds the documented withstand: the fixes are electrical or mechanical, not procedural. Reduce the available fault current at the bus, or re-brace and re-rate the assembly through the manufacturer, then recalculate on the new basis. Clearing time is not an option: the force is over before any protective device moves.
Questions asked
Does busbar force really vary with the square of the current?
Yes. The force between two parallel conductors equals the product of their two instantaneous currents times a geometry factor set by spacing and bar shape. Doubling the peak current multiplies the force by four, which is why the offset that raises the first-cycle peak by a factor of about 1.83 raises the mechanical duty by roughly 3.4.
Why does the worst force land in the first half-cycle?
A fault that begins at a voltage zero carries the largest DC offset, and that offset decays with the circuit's L/R time constant, about 45 ms at 60 Hz when the X/R ratio is 17. By the first AC peak, roughly 8.3 ms in, little of the DC component is gone, so the first peak is nearly the fully offset value and later peaks are smaller.
Is the available fault current figure enough for the bus check?
No. Available fault current, whether from a study or an equipment label, is a symmetrical RMS value intended for comparison with interrupting and withstand ratings. The bus-force calculation needs the first-cycle asymmetric peak built from that value plus the X/R at the bus, so using the RMS figure alone understates the mechanical duty.
Will a faster breaker clear the force away?
No. The electrodynamic peak occurs before any protective device can operate, within roughly the first half-cycle of the fault. Faster clearing limits thermal damage and arc-flash energy, but the only ways to cut the magnetic force are lower available fault current, wider conductor spacing, or heavier bus bracing.
