Choosing motor starters and PLC coil interface for 1.5 hp motors

Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

Both motors take the same starter: a 9 A AC-3 class contactor with a 110 V AC coil and an overload relay whose dial range brackets the nameplate FLA, which is the frame the recovered auger parts already use. Relay outputs switch the coils directly when rated for the pickup load; transistor outputs need a 24 V DC interposing relay. The clutch/brake timed command gets its own switching device.

On this page
  1. One duty class for both motors
  2. Selecting each device for this machine
  3. What to do with the recovered starters
  4. Worked example: sizing the starter for a 1.5 hp, 220 V three-phase motor
  5. Relay outputs versus transistor outputs
  6. Commissioning checks
  7. The decision for each position
  8. Questions asked

Your machine needs two identical starters and one separate interface decision. Both motors are 1.5 hp, 220 V three-phase, so each position takes a 9 A AC-3 class contactor (the LC1K09-10F7 frame) with a 110 V AC coil and an overload relay whose dial range brackets the motor's nameplate FLA. On the PLC side, the coil decides, not the motor: a relay output rated for the inductive pickup switches the coil directly, while a 24 V DC transistor output gets an interposing relay. The auger's clutch/brake is a third switching duty and never shares the motor contactor.

One duty class for both motors #

The agitator takes operator start and stop commands, so its contactor sees occasional starts of a squirrel-cage motor. The auger motor runs for the whole shift while a clutch/brake indexes the auger, so its contactor sees even fewer starts. Both land in the same utilization category: IEC 60947-4-1 places the starting and switching off of squirrel-cage motors during running in AC-3, and reserves AC-4 for starting, plugging and inching. Selection under those categories keys on the share of jogging and plugging in the duty cycle, which here is near zero, so AC-3 ratings govern both positions — the method in IEC contactor sizing by motor kW and duty class applies directly.

Selecting each device for this machine #

The starter comes from motor data and the interface comes from coil data; nothing else in the panel decides either one.

Position Choice Basis
Motor contactor, both motors 9 A AC-3 class with a 110 V AC coil, the LC1K09-10F7 frame Identical motors take identical starters, and this size sits well under that rating
Overload relay, both motors One dial range that brackets nameplate FLA, dial set to the nameplate value Two different relay types cannot both be right for identical motors
PLC relay output Direct coil switching where the output's inductive rating covers coil pickup The output carries coil current, not motor current
PLC transistor output Interposing relay with a 24 V DC coil, its contact rated for the AC coil A transistor output cannot switch an AC control circuit
Clutch/brake command Its own relay or contactor sized to the clutch coil inrush and operations per hour The indexing device, not the motor contactor, takes the frequent cycles
Branch short-circuit device Retain the branch fuse or breaker The overload relay is not a fault-clearing device

On the overload row: NFPA 70, the National Electrical Code, 2023 edition, covers motor branch circuits in Article 430 and sizes the overload device from the motor's nameplate full-load current rather than the table values — confirm the application with your authority having jurisdiction. The dial allowances are worked through in setting overload relays from motor nameplate full-load current.

What to do with the recovered starters #

As found, the auger assembly pairs an LC1K09-10F7 contactor with an LR2K0312 overload, and the agitator assembly pairs an LC1K06-10F7 with an LR2K0308. Both are recorded with 110 V coils, so read the coil marking yourself, AC and frequency included, before building on them.

Two different overload types on two identical motors cannot both be right. Read the dial range printed on each relay: keep the one whose range brackets the motors' nameplate current and fit its twin on the second motor; the other becomes a spare for a different motor. The contactor decision is the same — one frame for both positions, the 09 frame the auger assembly already has. The 06 frame goes to the spares shelf unless its data sheet shows an AC-3 rating at your supply that still covers the nameplate current; mixed frames buy nothing and invite a wrong swap later.

Before any of that: isolate the panel, lock it out, and test for absence of voltage at every terminal you will touch — NFPA 70E, 2024 edition, defines the electrically safe work condition — then inspect contacts, terminals and the overload mechanisms for heat damage, wear and modifications.

Worked example: sizing the starter for a 1.5 hp, 220 V three-phase motor #

Inputs:

  • Shaft output 1.5 hp, from the machine's motor data.
  • Supply 220 V, three-phase, as recorded on the machine; confirm it at the starter terminals.
  • Efficiency 0.80 and power factor 0.80 — example assumptions for a small machine motor, replaced by the nameplate FLA once you read it.

Rule: the per-phase current equals the shaft power divided by the product of √3, the line voltage, the efficiency and the power factor.

Arithmetic:

  • 1.5 hp × 745.7 W/hp = 1119 W
  • √3 × 220 V × 0.80 × 0.80 = 1.732 × 220 V × 0.64 = 243.9 V
  • I = 1119 W ÷ 243.9 V = 4.6 A

Result: about 4.6 A per phase, inside the 4 to 6 A band expected for this size — an estimate for selection, with the nameplate as the governing number.

Decision, with its threshold: a nameplate FLA at or below the contactor's AC-3 rating passes, and 4.6 A against 9 A passes with wide margin, since the AC-3 rating already includes across-the-line starting. A nameplate above the contactor rating moves you one frame up. The overload you keep must have a printed dial range that brackets the nameplate value; a relay whose range sits entirely above or below it is the wrong relay whatever its condition.

Relay outputs versus transistor outputs #

A relay output is an isolated contact. Fed from the control supply, it can switch the contactor coil directly, provided its voltage, inductive-load and operating-life ratings cover the pickup and the group current on a shared output common stays within the group limit — what relay rating a contactor coil switching circuit needs works that rating through. An AC coil draws a pickup current many times its sealed current, so a rating that covers only the sealed value is how outputs and relay contacts die.

A transistor output switches a DC circuit only, so for the AC coils here the interface is an interposing relay: a 24 V DC coil matched to the output — sourcing or sinking, and within its current rating — driving a contact that switches the control circuit. That contact faces the coil's pickup on every operation; why an interposing relay welds on contactor coil inrush is the failure you are sizing against. Put a diode across the DC relay coil, polarity observed; the AC coil takes the suppressor its manufacturer specifies.

Wire the overload trip contact into the coil circuit so a trip drops the contactor electrically, not only in software — wiring overload relay contacts to the coil and the PLC shows both paths. The PLC run command is ordinary control: stop pushbuttons and any safety function stay hardwired, and outputs should be configured so a latched command cannot restart the machine when power returns.

Commissioning checks #

With the panels closed and motion under the machine's approved test procedure:

  • Command each contactor from the PLC and confirm pickup, quiet seated holding and clean release; measure coil voltage while seated, because a chattering contactor is a pickup measurement, not a bench one.
  • Check rotation, then clamp all three phases under load and compare with the nameplate; chase any imbalance or sustained overcurrent before production.
  • Prove every stop path — the overload trip mechanism, removal of the run command, the machine's stopping function — and the power-restoration behaviour.
  • Time the clutch/brake against measured shaft motion, separating electrical delay from clutch slip or late braking.

The decision for each position #

  • Agitator motor: the 9 A AC-3 frame (LC1K09-10F7), coil at the control voltage you confirm on the existing parts, overload dial at nameplate FLA, operator run command through the PLC with a hardwired stop path.
  • Auger motor: the same starter; run the motor continuously while the machine is enabled and index with the clutch/brake device.
  • Interface: relay outputs switch the coils directly where their ratings cover pickup; transistor outputs always get the DC interposing relay.
  • Recovered hardware: both starters on the 09 frame, plus the overload whose dial range brackets the nameplate current and its twin.

Questions asked

Is the overload relay also the short-circuit protection for each motor?

No. The overload heats with motor current and trips on a sustained overload, but it has no interrupting capacity to clear a bolted fault. Keep the branch-circuit fuse or breaker, sized from the motor tables in NFPA 70, 2023 edition, and confirm the application with your authority having jurisdiction. Running protection and fault protection are different jobs.

What suppressor fits a 110 V AC contactor coil?

An RC network matched to the coil, fitted across its terminals. A diode is wrong on an AC coil: it suits DC only, with polarity observed, and on an AC supply it distorts the voltage the coil sees. Suppression also slows release, so on the clutch/brake circuit verify the release time before locking the PLC pulse width into the program.

Can I keep the smaller contactor from the agitator assembly?

Only if its data sheet shows an AC-3 rating at your supply that still exceeds the nameplate FLA. With two identical motors, one frame for both positions halves the spares inventory and removes the chance of a wrong-frame swap later, so the 09 frame is the default for both. The smaller frame becomes a spare for a genuinely smaller motor.

Why not index the auger by starting the motor for every dispense?

Each dispense would become a motor start, and contactor selection keys on how much of the duty cycle is jogging and plugging. Frequent indexing pushes the duty toward AC-4, which demands a larger contactor, and every start spends electrical life. A motor that keeps running with a clutch/brake doing the indexing takes that wear in a device built for frequent engagement.

Keep reading

  • Troubleshooting

    Why only one contactor pole burns on a small motor

    A single burnt pole on a small three-phase motor contactor is almost always one of two errors: a motor conductor landed on the normally open auxiliary contact, which carries only a control-circuit AC-15 rating, or a frame chosen on its AC-3 rating while the machine also jogs and plugs in AC-4. On the reported case the motor power exceeds the frame's AC-4 rating, so re-route the phase, select for the severe duty, and treat supply unbalance as the last suspect.

    Motors and motor starters

  • Selection guide

    Overload relay range selection for an 18.5 kW motor

    Select the relay by the motor's nameplate full-load current, not by kilowatts: pick the adjustable range that brackets that current away from both dial ends, then set the trip class from the measured acceleration time — class 10 for starts under 10 seconds, class 20 up to about 20. An 18.5 kW motor on a 400 V supply works out near 35 A; verify against the nameplate before you buy.

    Motors and motor starters

  • Selection guide

    Selecting DOL starter components for a single phase motor

    For a 0.55 kW single phase motor with a nameplate FLC of 4.6 A, select the motor circuit breaker GV2LE10 (6.3 A), the overload relay LRD10 (4–6 A) set to 4.6 A, and contactor LC1D09M7 from the Type 2 coordination table, and wire two poles of both protective devices in series.

    Motors and motor starters