Explainer

One motor protection relay on two motors hides an overload

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

A single motor protection relay measures only the summed current of two motors, so two 50 A motors on a 100 A setting with a 115% release never register one motor overloaded at 107.5 A total. Fit an overload relay on each motor wired to drop the shared contactor, or a relay per motor with a hard-wired cross-trip.

On this page
  1. One current input, one motor
  2. Worked example: two 50 A motors on a 100 A setting
  3. Why "the motors always run together" does not save it
  4. A separate overload relay on each motor
  5. Two protection relays with a cross-trip link
  6. Running status needs its own per-motor signal
  7. Checks before the motors restart
  8. Questions asked

A motor protection relay with one current input cannot protect two parallel motors by itself: it measures the sum of both feeder currents and judges every current-based function, thermal overload first among them, against one setting. On two equal motors, an overload on one motor plus a running partner lands below the trip point, so the relay never acts while that motor cooks. The fix is per-motor overload elements: an overload relay on each motor with its trip contact wired to drop the shared contactor and report into the relay, or a protection relay on each motor with a hard-wired cross-trip so either trip stops both. The sections below run the arithmetic that hides the overload, then the two wirings that fix it.

One current input, one motor #

Everything the relay knows about the load arrives through one current sensor. The thermal model, the overload alarm and trip, stall detection, current limits, no-load monitoring and the running status are all calculations on that single measured value. Put two motors in parallel behind the shared contactor and the sensor reads the two feeder currents added together; the relay cannot attribute a single ampere to a named motor.

The documentation for this class of motor protection relay states the scope without hedging: the device is designed to protect and control one motor, and with two motors in parallel behind one unit every current-based monitoring function works on the sum of both motor currents. The same guidance answers the two-motor question directly, install separate overload protection devices, because the summed measurement cannot see an overload on one motor while its partner runs light or has stopped.

Your existing starter makes the same point in hardware. The DOL starter this arrangement replaces carries one overload relay per motor, two current paths and two thermal models, because per-motor thermal protection needs per-motor current sensing. Swapping that starter for one protection relay does not fold both protections into the new device; it removes one of them.

Worked example: two 50 A motors on a 100 A setting #

Inputs, from the example case for this topic, the same numbers the relay maker's guidance uses in its own two-motor example:

  • Each motor's nameplate full-load current: 50 A, service factor 1.0.
  • Relay set current: 100 A, the sum of the two nameplate ratings.
  • Relay overload stage: releases on current above 115% of the set current, the release value in the maker's example; check your own relay's release setting in its manual.

The rule in words: the relay trips when the summed current exceeds its release threshold long enough for the thermal stage to time out, and reading overload relay trip classes and curves explains that timing. The overload the design must catch is set by code, not by the relay: NFPA 70, the National Electrical Code, 2023 edition, Article 430 covers motors and motor circuits, and 430.32 sizes a separate overload unit at 125 percent of nameplate full-load current for a motor marked with a service factor of 1.15 or higher or a temperature rise of 40 °C or less, and 115 percent for the rest. Confirm that requirement with your authority having jurisdiction and the equipment documentation.

Arithmetic:

  • Release threshold: 1.15 × 100 A = 115 A.
  • One motor pushed to its code-band overload point: 1.15 × 50 A = 57.5 A.
  • Total the relay measures, with the healthy partner at rated current: 57.5 A + 50 A = 107.5 A.
  • 107.5 A sits below the 115 A threshold, so the stage never releases and the thermal model never times out.

Result: one motor is at its full overload point while the relay reads 7.5 A below its own trip value. Nothing trips, and the overloaded motor's insulation takes the heating. If the partner motor stops at its isolator, the sum falls to the overloaded motor alone and the relay moves further from tripping, not closer.

Decision: for two equal motors the release threshold sits above twice one motor's rating, so an overload on one motor plus a partner at or near rated current always lands below it. That is structural, not a setting problem: summed protection cannot protect these motors, and each feeder needs its own overload element.

Why "the motors always run together" does not save it #

Run the assumption to ground before trusting it. Identical nameplates do not guarantee equal current: belt tension, voltage unbalance and supply impedance split the load between two parallel motors continuously, and only a per-motor measurement sees which one runs hot. A rigidly coupled pair on one gearbox is the strongest version of the argument, and even there the sum hides a broken coupling, because when one motor lets go of the load its current drops, its partner picks up the entire driven load, and the total can stay inside the release band while one motor runs near double its rating. Any mode where one motor is isolated for maintenance or trips on its own device breaks the assumption completely, because the healthy partner's current no longer tops up the sum.

This is the same mechanism that lets two motors share one plain overload relay and still end with a burned winding; why two motors behind one overload relay trip or burn follows that failure to its end.

A separate overload relay on each motor #

This is the fix the equipment guidance asks for, and it keeps the protection relay in the panel. Fit one overload relay per motor in its own feeder and set each device from that motor's nameplate full-load current inside the code band from the worked example; setting overload relays from motor nameplate full-load current covers the adjustment. Keep the relay's set current at the sum, because the sum stays valid for what remains: current limits, stall checks, no-load monitoring and the bus.

Wire the trip contacts so a trip on either motor de-energizes the shared contactor coil, and take the same contact in parallel to a relay input configured as an external fault so the trip reaches the alarm list; wiring overload relay trip contacts to the coil and the PLC shows that contact arrangement. With one shared contactor, either trip stops both motors; if the process needs one motor to keep running, each motor needs its own contactor and its own relay instead.

Function Handled by
Per-motor thermal overload one overload relay per motor, set from its own nameplate
Contactor control and communications the motor protection relay
Current limits, stall and no-load checks the motor protection relay, on the summed current
Either trip dropping the load trip contact in the coil path, reported as an external fault

Where you want per-motor current data, diagnostics and event history, give each motor its own device. Each one measures its own feeder and runs a real thermal model on it, which removes the summed-current problem at the source.

Mutual tripping then has to be built in. Take a trip output contact from each device to a digital input of the other, configured as an external fault whose response trips rather than alarms, and either device drops its own contactor when its partner trips. Hard-wire that link instead of trusting the fieldbus: a hard-wired cross-trip keeps working with communications down, while a bus-only interlock dies with the connection.

If the interlock carries a safety function, this relay class offers fail-safe expansion modules for the job; a standard trip contact and input pair is the documented path for a process interlock. Decide the reset behavior too, so both devices must be reset before either motor can restart; otherwise one motor can restart alone against a partner that tripped.

Running status needs its own per-motor signal #

The relay's running status also lives on the summed current, and its recognition threshold has to sit well below one motor's part-load current for the function to work at all, so a single healthy motor clears it easily. Start one motor while the other sits jammed and the relay reports the load running with half of it dead.

Build the confirmation from hardware. A spare auxiliary contact from each motor contactor goes to separate inputs on the protection relay or the controller; make the running condition true only when both inputs are present, and alarm when a commanded run has no matching confirmation. The same limit applies to the undercurrent or no-load alarm: it watches the total, so it catches a complete loss of load, not the quiet loss of one motor. Only per-motor signals see that.

Checks before the motors restart #

De-energize the cubicle, lock it out and verify absence of voltage at the terminals before any of this wiring. Anything that needs the panel open with power on is energized work under your plant's arc-flash program, which NFPA 70E, 2024 edition, covers as electrical safety-related work practices, and it needs that program's permits and protective equipment.

With the panel closed and the motors available, verify the design end to end:

  • Run both motors, stop one at its isolator, and watch the relay's measured current fall to the remaining motor's current. That confirms the sensor reads both feeders and nothing else.
  • Press the test function on each overload relay in turn: the shared contactor must drop, the external-fault input must show on the protection relay, and restart must stay blocked until you reset the relay and the device.
  • Run each motor alone under light load and record its current; confirm each relay's setting against its own motor's nameplate and the code band.
  • Disconnect the fieldbus and trip one relay: with the hard-wired cross-trip, the other motor must still stop.
  • Re-check the summed functions, current limits, stall, no-load and running status, against the total, now that thermal protection no longer depends on them.

Questions asked

Why does the relay never trip when one of two parallel motors overloads?

It holds one measurement: the sum of both feeder currents. In the example, two motors rated 50 A with the relay set to 100 A and the overload stage releasing at 115% trip at 115 A. One motor at its 57.5 A overload point plus its partner at rated current reads 107.5 A, under the trip value, so nothing acts. Tuning cannot fix it either: a threshold low enough to catch that sum sits too close to the normal two-motor running current.

With one shared contactor, what happens when one motor's overload trips?

Both motors stop, because either trip contact opens the one contactor coil path. If the process needs one motor to keep running while its partner is down, each motor needs its own starter: contactor, short-circuit protective device and overload relay, plus cross-trip wiring so a trip on one still shuts the other down.

Can the cross-trip between two relays go through the PLC instead of wiring?

You can, if the interlock has no safety function and you accept the network as part of the trip path: one device reports its trip on the bus and the controller commands the other device to stop. If communications or the controller is out, the interlock is out, so hard-wire the link when the two motors must always stop together regardless of the network.

What happens to the summed readings after the per-motor relays are installed?

Leave the protection relay's set current at the sum of the two nameplate currents. The summed value stays valid for current limits, stall checks, no-load monitoring and the bus, while thermal protection now lives entirely in the per-motor relays. Expect summed readings to halve when one motor runs alone, so set summed alarms with single-motor running in mind.

If both motors are identical and always run together, is one relay enough?

The arithmetic still fails: the trip threshold sits above twice one motor's rating, so an overload on one motor plus a partner at rated current stays below it. Unequal loading, a stopped motor or a broken coupling widens the gap, and the guidance for these relays is to fit a separate overload relay on each motor regardless.

Keep reading

  • Troubleshooting

    Why two motors behind one overload relay trip or burn

    Set one overload relay per motor winding, sized from that winding's own nameplate full-load current. A shared relay set to the combined current lets a single winding run near twice its rating before tripping, and a shared relay set to one winding's rating trips on normal running current. NFPA 70 Article 430, Part III requires individual motor overload protection.

    Motors and motor starters

  • Selection guide

    Overload relay range selection for an 18.5 kW motor

    Select the relay by the motor's nameplate full-load current, not by kilowatts: pick the adjustable range that brackets that current away from both dial ends, then set the trip class from the measured acceleration time — class 10 for starts under 10 seconds, class 20 up to about 20. An 18.5 kW motor on a 400 V supply works out near 35 A; verify against the nameplate before you buy.

    Motors and motor starters

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.

    Motors and motor starters

Thermal overload relay current injection test in a 25°C MCC