Reversing starter pedal control: coil pulls in but motor stays dead

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

A pulling coil proves the control circuit, not the power circuit. Check the five places the load path can stop — line voltage, seated armatures, the links between the two contactors, installed overload heaters, motor leads moved from drum switch to T terminals — then wire the pedal as two-wire momentary control with the seal-in contacts removed.

On this page
  1. Where the power stops when the coil pulls in
  2. Two-wire momentary or three-wire latched
  3. Wiring the conversion, step by step
  4. Worked example: coil voltage margin at 110 V control
  5. Reading the fault from the meter
  6. Jogging duty and the starter's real rating
  7. Questions asked

Both coils pulling in is the strongest diagnosis this circuit can give: the control side works, and the dead motor lives downstream of it. Between the line lugs and the motor leads there are exactly five places the current can stop, and one of them owns this fault — in a drum-switch-to-reversing-starter conversion it is most often the heater pockets or the leads that never moved. Wire the pedal the way the drum behaved: two-wire momentary control, seal-in contacts lifted, electrical interlocks kept, one master stop ahead of both branches. The fault is the mirror image of a starter coil that has voltage but won't pull in — there the coil is the suspect, here it is the proof.

Where the power stops when the coil pulls in #

The coil, its branch, the interlocks and the overload trip contact all sit upstream of the load terminals, and they just proved themselves. Walk these five points in order, with a meter rather than by ear:

  1. No source at the line lugs. An open disconnect, a blown fuse, or line and load transposed during the conversion. Measure phase-to-phase at L1, L2 and L3 with the disconnect closed; no reading there ends the hunt at the source.
  2. An armature that buzzed but never seated. An audible pull-in is not a closed pole. Undervoltage on the coil, a jammed mechanical interlock, or both contactors energized at once can hold the main contacts open while the magnet sounds healthy.
  3. Interconnecting links missing between the two contactors. Reversal is two contactors bussed together — one set straight through, two phases transposed on the other, which is the arrangement described in why reversing a three-phase motor needs two contactors. Strip the links out and each contactor closes onto nothing.
  4. Empty overload heater pockets. NEMA overload blocks commonly ship without heater elements, and the heaters carry motor current in series with the load terminals, so empty pockets are a closed contactor feeding an open circuit. The heaters also set the trip class: a Class 20 relay trips in 20 seconds or less at 600% of its rating. The relay's normally closed contact is not the suspect — the coils pulled in, so that contact is closed; the heaters and their terminations are. Where that contact belongs is its own wiring question, covered in wiring overload relay contacts to the coil and the PLC.
  5. Motor leads still landed where the drum switch sat. The conversion moves phase reversal from the drum's contacts into the starter, and until the leads move to T1, T2 and T3 the starter feeds nothing.

Two-wire momentary or three-wire latched #

The factory three-wire diagram puts a momentary start contact in series with each coil, a normally open auxiliary in parallel with it, and a normally closed stop ahead of the branches. The auxiliary is the seal-in: press start, the coil pulls, the auxiliary closes and holds the coil after the button releases. Nothing in that loop opens by itself — which is why the stop button exists and why a pedal alone would never stop a latched motor.

A foot pedal wants the other scheme. Two-wire momentary control drops the seal-in entirely: the coil is energized exactly while the operator is held, which reproduces the drum switch's behavior with contactors.

Two-wire momentary (pedal) Three-wire latched
Operators pedal NO and pushbutton NO start NO, stop NC, seal-in aux
Seal-in contact removed required
Release behavior coil drops when the operator opens coil holds until stop is pressed
After a voltage dip restarts if the operator is still held stays off until start is pressed
After an overload reset restarts if the operator is still held stays off
Fits a foot pedal yes no

That restart row is the character of the scheme: the output follows the input with no memory, the same no-latch pattern described in the knowledge-base article on an autosteer that re-engages after an overcurrent because nothing latches. It is also why the master stop earns its place: keep one NC stop block ahead of both branches, because a jammed or welded pedal leaves that block as the only device that clears both coils. It is a control stop, not a validated safety function — that distinction is treated on its own in when an e-stop motor starter circuit is a validated safety function.

Decision: two-wire momentary is the scheme for this conversion. If the drum switch were being replaced by a drive instead of contactors, the same two operators would land on the drive's own control terminals — a different wiring job, covered in wiring start and stop pushbuttons when a VFD replaces a DOL starter.

Wiring the conversion, step by step #

Before any cover comes off, lock the disconnect and verify absence of voltage at the line lugs and across both coil terminals with a low-impedance meter, because a starter switched off still leaves its line side energized, as why a switched-off breaker leaves its line side energized explains. NFPA 70E, 2024 edition, frames that de-energize-and-verify step as the gate for opening a panel; confirm the details with your authority having jurisdiction and the starter's documentation.

  1. Match the coil stamp to the control source. A coil fed below its pickup band hums and half-seats, which mimics a healthy contactor that passes no current.
  2. Move the control supply leads if control is separate from the power lines. The typical Bulletin 505 wiring diagram marks two control leads, A and B, that lift off L1 and L2 and land on the separate control source. Never backfeed an outside supply into a circuit that already has a fused, grounded control-transformer secondary.
  3. Lift both seal-in auxiliary contacts — the ones in parallel with the start buttons on the factory diagram. Removing them is the conversion from latched to momentary.
  4. Keep the normally closed electrical interlock in series with each coil. If the starter carries only the mechanical interlock, add the electrical one: reversing hardware kits supply the mechanical interlock, stabilizer bar and wire set, and auxiliary contacts come as separate accessories. The mechanical interlock stops both armatures seating; it does not stop both coils drawing current.
  5. Leave the overload relay's normally closed contact in the common return so it drops both branches.
  6. Land the pedal NO contact in series with the forward coil branch and the pushbutton NO contact in series with the reverse branch. The pedal contact's rating is three numbers, covered in why a trip pushbutton contact rating is three numbers; match them against the coil.
  7. Put the master NC stop ahead of the branch point.
  8. Walk the power path with an ohmmeter: line lugs, contactor poles, the cross links, every heater pocket, out to T1, T2 and T3.
  9. Torque every power and control termination to the value printed on the starter's label.

Worked example: coil voltage margin at 110 V control #

Inputs, with their sources:

  • Control supply: 110 V AC measured across X1 and X2, the source this conversion uses — the 505-AOD installation runs on 110 V control.
  • Coil: rated for that same control circuit, confirmed against the stamp.
  • Operating band: pick-up and hold between 85% and 110% of rated control supply voltage, the limits IEC 60947-4-1 (2018 edition), the low-voltage contactor and starter product standard, places on an AC magnet coil; confirm the exact band against the starter's own coil data.

Rule: a coil fed anywhere inside the band picks up and holds solid; below the low end the magnet can buzz and partially seat, leaving the power poles open while the coil looks alive — that is point 2 of the five above, not a dead coil.

Arithmetic: low end 110 V × 0.85 = 93.5 V; high end 110 V × 1.10 = 121 V.

Result: with the pedal held, a reading between 93.5 V and 121 V at the coil terminals proves the coil side; a full-source measurement sits mid-band.

Decision: a held-pedal reading in the 93.5 V to 121 V band clears the coil, and the hunt moves to the five power-path points. A reading under 93.5 V is its own fault — a sagging control transformer or a long, thin control feed — and it explains a buzzing, half-seated contactor before the power side is touched at all.

Reading the fault from the meter #

What you measure Mechanism Confirming check
Coils energized, no continuity through any pole Armature not seated Coil voltage at its own terminals while held, against the pickup band; confirm the two contactors are not energized together
Poles ohm out closed, no voltage at the line lugs No source Phase-to-phase at L1, L2 and L3 with the disconnect closed
Voltage at the contactor load terminals, none past the overload Missing or open heater elements Continuity through each heater pole; heater size against the motor's full-load current
One direction runs, the other dead Cross links between the contactors missing Continuity from the dead contactor's line terminals back to the lines
Two phases live at the motor, one dead; motor hums Single-phasing — one link, fuse or heater open All three phases at the motor terminal box under load
Voltage shows on a non-contact tester only Ghost voltage Re-measure phase-to-phase with a low-impedance meter

Jogging duty and the starter's real rating #

Every pedal tap is an inrush event with no run time between taps to cool the contact tips, and a NEMA starter carries a separate jogging and plugging rating below its standard-duty horsepower. That rating is published for each starter size in the manufacturer's literature; the wiring diagrams and trip-class definitions do not restate it, so it comes from the rating table, not from a rule of thumb. The decision is direct: pedal duty is rated duty, so a starter chosen to barely clear the motor's running horsepower is the wrong starter under a footswitch — verify the jogging rating against the motor before the pedal goes into service. Expect the correctly sized overload to trip if tap-tap-tapping keeps the motor near locked-rotor current; the relay is doing its job, and the fix is run time between taps, not bigger heaters.

Questions asked

Can I leave the stop button out because the motor already has an electric brake?

The brake holds the load but says nothing about the circuit. If the pedal contact welds closed with the pedal down, the coil stays energized and the motor sits stalled against the brake, heating both. The stop block opens the coil circuit and lets the brake do its work, and it opens forward and reverse with one press. One contact position buys that.

Will a coil stamped 120 V work on this control circuit?

Yes. The operating band around a 120 V coil runs from 102 V to 132 V — 85% to 110% of rating — and a 110 V supply sits inside it with margin. The coil to worry about is a 240 V unit on this source: it sits far below pickup and only buzzes and half-seats, which looks exactly like a healthy contactor that passes no current. Read the stamp before wiring.

What trip class suits a motor that jogs all day?

The class sets trip time at six times rated current: a Class 20 relay trips in 20 seconds or less at 600% of rating, a Class 10 in 10 seconds, a Class 30 in 30. Match the class to the motor's acceleration time and locked-rotor withstand from its data, not to the duty; a load that takes long to accelerate needs the higher class, and constant nuisance trips point first to heater size against full-load current.

Does the footswitch contact need a special rating for coil inrush?

It needs a pilot-duty contact block whose three ratings — AC make, AC break and continuous carry — clear the coil's inrush and sealed current from the starter's data sheet. An AC coil draws several times its seated current while the armature is moving, and a pedal contact undersized for that make value erodes and welds early. A standard contact block rated for AC pilot duty on the starter's coil size is the right part.

Can two pedals run the same direction?

Yes, in two-wire control. Put the two pedal contacts in parallel inside the same coil branch: either pedal closing energizes that direction's coil. Never bridge the two direction branches together — the normally closed electrical interlock in each branch is what blocks both coils from energizing at once, and a parallel tie across the branches defeats it. Two operators, one direction, is simply an OR of the contacts.

Keep reading

  • How-to

    Reversing rotation on a star-delta starter: which two phases

    For a one-time direction change, exchange any two incoming phases at the dedicated supply termination ahead of the entire starter and leave every star and delta connection untouched: the rotating field follows the phase sequence, so the star start and the delta run reverse together. For forward and reverse in normal operation, add a mechanically and electrically interlocked reversing contactor pair upstream and close it before the star-delta sequence begins.

    Motors and motor starters

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters

  • How-to

    Identifying terminals on an old star-delta starter panel

    A1 and A2 are the contactor coil terminals, and the coil's labeled voltage must sit within the 85 to 110 percent band IEC 60947-4-1 requires against the control supply. NO only means a contact is open at rest; its traced wiring decides whether it is a start or holding contact. With the panel locked out and verified dead, tracing the six motor leads through the contactors is what proves a star-delta scheme.